Technical Specifications - GE BA300 Commissioning Instructions

Battery alarm for use with substation and telecontrol batteries
Table of Contents

Advertisement

Before energising the equipment, the following should be checked:
Voltage rating and polarity;
Protective fuse rating;
Integrity of earth connection
Equipment operating conditions
The equipment should be operated within the specified electrical and
environmental limits.
Insulation and dielectric strength testing
Insulation testing may leave capacitors charged up to a hazardous voltage.
At the end of each part of the test, the voltage should be gradually reduced to
zero, to discharge capacitors, before the test leads are disconnected.
Disposal
It is recommended that incineration and disposal to water courses is avoided.
The product should be disposed of in a safe manner.

Technical Specifications

Protective fuse rating
The recommended maximum rating of the external protective fuse for this
equipment is 2A, Red Spot type or equivalent.
Insulation class: IEC 61010-1:
Class I
EN 61010-1:
Class I
Installation
IEC 61010-1:
Category
Category III
(Overvoltage): EN 61010-1:
Category III
Environment:
IEC 61010-1:
Pollution degree 2
EN 61010-1:
Pollution degree 2
Product safety: 73/23/EEC
EN 61010-1:
EN 60950:
1990/A2:
1995
1993/A2:
1995
1990/A2:
1995
1993/A2:
1995
1990/A2:
1995
1993/A2:
1995
1993/A2:
1995
1992/A11: 1997
Page 5
This equipment requires a
protective (safety) earth
connection to ensure user
safety.
Distribution level, fixed
installation. Equipment in
this category is qualification
tested at 5kV peak,
1.2 50µs, 500Ω, 0.5J,
between all supply circuits
and earth and also
between independent
circuits.
Compliance is
demonstrated by reference
to generic safety standards.
Compliance with the
European Commission
Low Voltage Directive.
Compliance is
demonstrated by reference
to generic safety standards.