Installing or Replacing Modules, Fan Trays, and Power Supplies
This example specifies Cisco NX-OS Release 8.3(1) images. This is the minimum software release for the
Note
Cisco Nexus 7700 Series Supervisor 3E modules.
Caution
Use -s3- images with Supervisor 3E modules. If you use an -s2- image with a Supervisor 3E module, the
supervisor will not boot up. Some examples of an -s2- image are given below:
• n7700-s2-kickstart.8.0.1.bin
• n7700-s2-kickstart.8.1.1.bin
• n7700-s2-kickstart.8.2.1.bin
Step 6
Turn off the power to the switch using the power switch on each power supply. The Output LED turns off on each
power supply and the Status LEDs turn off on all of the supervisor and I/O modules.
If any of the supervisor or I/O module Status LEDs is turned on (showing any color), stop at this step until
Caution
you are able to turn off those modules.
Step 7
For each Supervisor 2E module installed in the switch, remove the module and replace it with a Supervisor 3E module
as explained in
Caution
If the switch has two supervisor modules, ensure that both supervisors are of the same type. Do not mix
Supervisor 2E modules with Supervisor 3E modules.
Step 8
Power up the switch by using the power switch on each of its power supplies. The Output LED on each power supply
turns on and eventually turns green when the power supply is sending power to the switch. The Status LED on each
installed supervisor module also turns on when the module begins to turn on. The supervisor that becomes active has
a green ACTIVE LED (the standby supervisor module has an amber ACTIVE LED).
Step 9
Remove the USB drive from the Supervisor 2E module (this drive has copies of the Supervisor 2E configuration,
license, and software images) and insert it in the USB port on the active Supervisor 3E module (ACTIVE LED is green).
Step 10
Connect a console to the active supervisor module as explained in
Step 11
If you are setting up the initial configuration for the supervisor module, the initial setup script will ask you if you want
to enforce the secure password standard. Make your selection, enter your password, and then confirm the password by
entering it again.
---- System Admin Account Setup ----
Do you want to enforce secure password standard (yes/no) [y]:
Enter the password for "admin":
Enter the password for "admin":
Step 12
When you are asked to enable admin VDCs, enter no.
Do you want to enable admin vdc (yes/no) [no]: no
Step 13
When you are asked to enter the basic configuration, enter no.
---- Basic System Configuration Dialog VDC: 1 ----
This setup utility will guide you through the basic configuration of
the system. Setup configures only enough connectivity for management
of the system.
Please register Cisco Nexus7000 Family devices promptly with your
supplier. Failure to register may affect response times for initial
service calls. Nexus7000 devices must be registered to receive
OL-30452-01.
Migrating from Supervisor 2E Modules (N77-SUP2E) to Supervisor 3E Modules (N77-SUP3E)
Installing or Replacing a Supervisor Module, on page
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
87.
Connecting a Console to the Switch, on page
42.