Maximum Power Available For 3.5-Kw Inputs (Dc) - Cisco Nexus 7710 Site Preparation And Hardware Installation Manual

Table of Contents

Advertisement

Switch Specifications

Maximum Power Available for 3.5-kW Inputs (DC)

The maximum power available for operations depends on the input power from your power source, the number
and output capabilities of your power supplies, and the power redundancy mode that you use. The following
table lists the amount of power available for 3.5-kW HVAC/HVDC power supplies depending on DC power
inputs, numbers of power supplies, and the mode used.
Power Inputs
1 input (380 V)
1 input (220/240
V)
OL-30452-01.
Power Supplies
Combined Mode
1
3500 W
2
7000 W
3
10,500 W
4
14,000 W
5
17,500 W
6
21,000 W
7
24,500 W
8
28,000 W
1
3500 W
2
7000 W
3
10,500 W
4
14,000 W
5
17,500 W
6
21,000 W
7
24,500 W
8
28,000 W
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
Maximum Power Available for 3.5-kW Inputs (DC)
Power Supply
Input Source
Redundancy
Redundancy
Mode
Mode
3500 W
3500 W
7000 W
3500 W
10,500 W
7000 W
14,000 W
7000 W
17,500 W
10,500 W
21,000 W
10,500 W
24,500 W
14,000 W
3500 W
3500 W
7000 W
3500 W
10,500 W
7000 W
14,000 W
7000 W
17,500 W
10,500 W
21,000 W
10,500 W
24,500 W
14,000 W
Full Redundancy
Mode
3500 W
3500 W
7000 W
7000 W
10,500 W
10,500 W
14,000 W
3500 W
3500 W
7000 W
7000 W
10,500 W
10,500 W
14,000 W
145

Advertisement

Table of Contents
loading

Table of Contents