Supervisor Module LEDs

Supervisor Module LEDs
LED
STATUS
ID
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
192
Color
Status
Green
All diagnostics pass. The module is operational (normal initialization
sequence).
Amber
Indicates one of the following:
• The module has detected a slot ID parity error and will not power
on or boot up.
• The module is booting or running diagnostics (normal initialization
sequence).
• An over temperature condition has occurred. (A minor temperature
threshold has been exceeded during environmental monitoring.)
Flashing red
Indicates one of the following:
• The diagnostic test has failed.
• The module is not operational because a fault occurred during the
initialization sequence.
• An over temperature condition has occurred. (A major temperature
threshold has been exceeded during environmental monitoring.)
Red
The module has detected a slot ID parity error and will not power on
or boot up.
Off
The module is not receiving power.
The operator has activated this LED to identify this module in the
Flashing blue
chassis.
Off
This module is not being identified.