PG80VTLA: Installation, Start-up, Operating and Service and Maintenance Instructions
5. If equipped with factory-specified disposable media filter, replace
only with media filter having the same part number and size. For
expandable replacement media, refer to the instructions included
with the replacement media.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
Table 13 – Filter Size Information - In. (mm)
FILTER SIZE
FURNACE
SIDE
CASING WIDTH
RETURN
16 X 25 X 3/4
14-1/2 (368)
(406 X 635 X 19)
16 X 25 X 3/4
17-1/2 (445)
(406 X 635 X 19)
16 X 25 X 3/4
21 (533)
(406 X 635 X 19)
16 X 25 X 3/4
24 (610)
(406 X 635 X 19)
Recommended
*.
Blower Motor and Wheel
The following steps should be performed by a qualified service agency.
NOTE: The blower wheel should not be dropped or bent as balance will
be affected.
To ensure long life and high efficiency, clean accumulated dirt and
grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no
additional lubrication. These motors can be identified by the absence of
oil ports on each end of the motor.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access door switch opens 115-v power to control. No
component operation can occur unless switch is closed. Caution must
be taken when manually closing this switch for service purposes.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove outer door.
3. For downflow or horizontal furnaces having vent pipes within the
furnace that pass in front of the blower access door:
a. Disconnect vent connector from furnace vent elbow.
b. Disconnect and remove short piece of vent pipe from within
furnace.
4. Remove screws from blower access door and remove blower access
door.
5. All factory wires can be left connected, but field thermostat
connections may need to be disconnected depending on their length
and routing.
6. Remove 2 screws holding blower assembly to blower deck and
slide blower assembly out of furnace.
7. Clean blower wheel and motor using a vacuum with soft brush
attachment. Blower wheel blades may be cleaned with a small paint
or flux brush. Do not remove or disturb balance weights (clips) on
blower wheel blades.
8. Vacuum any loose dust from blower housing, wheel and motor.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
FILTER TYPE
BOTTOM
RETURN
14 X 25 X 3/4
Washable
(356 X 635 X 19)
16 X 25 X 3/4
Washable
(406 X 635 X 19)
20 X 25 X 3/4
Washable
(508 X 635 X 19)
24 X 25 X 3/4
Washable
(610 X 635 X 19)
9. If a greasy residue is present on blower wheel, remove wheel from
the blower housing and wash it with an appropriate degreaser.
NOTE: Before disassembly, mark blower mounting arms, motor, and
blower housing so motor and each arm is positioned at the same location
during reassembly.
To remove wheel:
a. Disconnect ground wire attached to blower housing.
b. Remove screws securing cutoff plate and remove cutoff plate
from housing.
c. Loosen set screw holding blower wheel on motor shaft (160+/-20
*
in.-lb. when assembling).
d. Remove bolts holding motor to blower housing and slide motor
out of wheel (40+/-10 in.-lb. when reassembling).
e. Remove blower wheel from housing.
f. Clean wheel and housing.
10. Reassemble motor and blower by reversing steps 9a, through 9e. Be
sure to reattach ground wire to the blower housing.
11. Verify that blower wheel is centered in blower housing and set
screw contacts the flat portion of the motor shaft. Loosen set screw
on blower wheel and reposition if necessary.
12. Spin the blower wheel by hand to verify that the wheel does not rub
on the housing.
13. Reinstall blower assembly in furnace.
14. Reinstall 2 screws securing blower assembly to blower deck.
15. Reconnect blower leads to furnace control. Refer to furnace wiring
diagram, and connect thermostat leads if previously disconnected.
16. To check blower for proper rotation:
a. Turn on electrical supply.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower access door switch opens 115-v power to furnace control. No
component operation can occur unless switch is closed. Exercise
caution to avoid electrical shock from exposed electrical components
when manually closing this switch for service purposes.
b. Manually close blower access door switch.
NOTE: If R-W/W1 thermostat terminals are jumpered at the time
blower access door switch is closed, blower will run for 90 sec before
beginning a heating cycle.
c. Perform component self-test as shown at the bottom of the
SERVICE label, located on the front of blower access door.
d. Verify blower is rotating in the correct direction
17. If furnace is operating properly, RELEASE BLOWER ACCESS
DOOR SWITCH. Remove any jumpers or reconnect any
disconnected thermostat leads. Replace blower access door.
18. Downflow or horizontal furnaces with vent pipe through furnace
only:
a. Install and connect short piece of vent pipe inside furnace to
existing vent.
b. Connect vent connector to vent elbow.
19. Reinstall outer door.
20. Turn on gas supply and cycle furnace through one complete heating
and cooling cycle. Verify the furnace temperature rise as shown in
Adjustments Section. Adjust temperature rise as shown in
Adjustments Section. If outdoor temperature is below 70_F, turn off
circuit breaker to outdoor unit before running furnace in the cooling
cycle. Turn outdoor circuit breaker on after completing cooling
cycle.