Carrier 58TP1A Installation, Start-Up, Operating And Service And Maintenance Instructions

80 per sent afue, variable-speed, ecm motor, two-stage, 4-way multipoise, non-condensing gas furnace,

Advertisement

Quick Links

58TP0A/58TP1A
80% AFUE, Variable-Speed, ECM Motor,
Two-Stage, 4-Way Multipoise,
Non-Condensing Gas Furnace, Series A
Read the entire instruction manual before starting the installation.

TABLE OF CONTENTS

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
CODES AND STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
DURE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
AIR FOR COMBUSTION AND VENTILATION . . . . . . . . . . . . 6
Table 1 - Minimum Free Area Required for Each Combustion Air
opening of Duct to Outdoors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 2 - Minimum Space Volumes for 100% Combustion, Ventila-
tion, and Dilution from Indoors . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
UPFLOW INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
DOWNFLOW INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 3 - Opening Dimensions - In. (mm) . . . . . . . . . . . . . . . . . 10
HORIZONTAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . 10
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
GENERAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . 12
SUPPLY AIR CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . 12
RETURN AIR CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . 12
GAS PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 4 - Maximum Capacity of Pipe . . . . . . . . . . . . . . . . . . . . . 14
ELECTRICAL CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 5 - Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
J-BOX RELOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
NOTES FOR FIGURES 28 - FIGURES 35: . . . . . . . . . . . . . . . . . . 19
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
GENERAL VENTING REQUIREMENTS . . . . . . . . . . . . . . . . 20
Table 6 - Combined Appliance Maximum Input Rating
in Thousands of Btuh per Hour . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 7 - Minimum Allowable Input Rating of
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
START-UP PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 8 - Altitude Derate Multiplier for U.S.A. . . . . . . . . . . . . . 27
Table 9 - Blower Off Delay Setup Switch . . . . . . . . . . . . . . . . . 28
Table 10 - Gas Rate (CU ft./hr). . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 11 - Orifice Size and Manifold Pressure (In. W.C.) for Gas Input
Rate (Tabulated Data Based on 22,000 Btuh High-Heat/14,500 Btuh
for Low-Heat per Burner, Derated 4 Percent for Each 1000 Ft.(305 M)
Above Sea Level). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1E, with permission of National Fire Protection Association, Quincy, MA
02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI
Installation, Start-up, Operating and
Service and Maintenance Instructions
on the referenced subject, which is represented only by the standard in its entirety.
Table 12 - Air Delivery - CFM (With Filter)* . . . . . . . . . . . . . . 33
SERVICE AND MAINTENANCE PROCEDURES. . . . . . . . . . . . 36
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Table 13 - Filter Size Information - In. (mm) . . . . . . . . . . . . . . . 38
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
PARTS REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . 47
EXAMPLE OF MODEL NUMBER . . . . . . . . . . . . . . . . . . . . . . . . 47
TRAINING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury and/or
death.
Carbon Monoxide (CO) is a colorless, odorless, and tasteless poisonous
gas that can be fatal when inhaled. Follow all installation, maintenance,
and service instructions. See additional information below regarding
the installation of a CO Alarm.
Most states in the USA and jurisdictions in Canada have laws that
require the use of Carbon Monoxide (CO) alarms with fuel burning
products. Examples of fuel burning products are furnaces, boilers, space
heaters, generators, water heaters, stoves/ranges, clothes dryers,
fireplaces, incinerators, automobiles, and other internal combustion
engines. Even if there are no laws in your jurisdiction requiring a CO
Alarm, it's highly recommended that whenever any fuel burning product
is used in or around the home or business that the dwelling be equipped
with a CO Alarm(s). The Consumer Product Safety Commission
recommends the use of CO Alarm(s). The CO Alarm(s) must be
installed, operated, and maintained according to the CO Alarm
manufacturer's instructions. For more information about Carbon
Monoxide, local laws, or to purchase a CO Alarm online, please visit the
following website. https://www.kidde.com.
NOTE: Read the entire instruction manual before starting the
installation.
A200103

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 58TP1A

  • Page 1: Table Of Contents

    58TP0A/58TP1A 80% AFUE, Variable-Speed, ECM Motor, Two-Stage, 4-Way Multipoise, Non-Condensing Gas Furnace, Series A Installation, Start-up, Operating and Service and Maintenance Instructions Read the entire instruction manual before starting the installation. Table 12 – Air Delivery - CFM (With Filter)* ....33 SERVICE AND MAINTENANCE PROCEDURES.
  • Page 2 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions A190045 ACCESSORY VENT SHIP WT. FILTER TOP AND FURNACE SIZE CONNECTION CABINET OUTLET BOTTOM LB (KG) MEDIA BOTTOM FLUE SIZE WIDTH WIDTH INLET WIDTH CABINET SIZE COLLAR 045V14-12 14-3/16 (360) 12-9/16 (319)
  • Page 3: Safety Considerations

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions SAFETY CONSIDERATIONS The following additional safety considerations should be followed for gas furnaces: WARNING 1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
  • Page 4: Introduction

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions INTRODUCTION A02054 Fig. 4 – Prohibit Installation on Back WARNING FIRE, INJURY OR DEATH HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. When the furnace is installed in a residential garage, the burners and A10269 Fig.
  • Page 5: Electrostatic Discharge (Esd) Precautions Proce

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions (SMACNA), or American Society of Heating, Refrigeration, and Air CAUTION Conditioning Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter 35 or 2005 HVAC Systems and Equipment Handbook Chapters PERSONAL INJURY AND/OR PROPERTY 9 and 16.
  • Page 6: Location

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions LOCATION CAUTION GENERAL This multipoise furnace is shipped in packaged configuration. Some FURNACE CORROSION HAZARD assembly and modifications are required when used in any of four Failure to follow this caution may result in furnace damage.
  • Page 7 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Table 1 – Minimum Free Area Required for Each Combustion Air opening of Duct to Outdoors TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS FURNACE (1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW) (1 SQ.
  • Page 8 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions 2. For fan-assisted appliances such as this furnace: than 100 in. (0.06 m ). One opening shall commence within 12 in. (300 mm) of the ceiling and the second opening shall commence within 12 in.
  • Page 9: Installation

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions b. Outdoor opening size reduction Factor is 1 minus the Ratio in a. 2. Rotate bottom filler panel downward to release holding tabs. above. 3. Remove bottom closure panel. c. Minimum size of Outdoor openings shall be the size required in 4.
  • Page 10: Horizontal Installation

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Table 3 – Opening Dimensions - In. (mm) PLENUM OPENING FLOOR OPENING FURNACE APPLICATION CASING WIDTH Upflow Applications on Combustible or Noncombustible Flooring 12-11/16 21-5/8 13-5/16 22-1/4 (subbase not required) (322)
  • Page 11: Location Relative To Cooling Equipment

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Not all horizontal furnaces are approved for side return air connections. (Refer to Horizontal Return Air Configurations and Restrictions (Fig. 20) in the “Upflow and Horizontal Furnaces” section.) Leveling Legs (If Desired) In upflow position with side return inlet(s), leveling legs may be used.
  • Page 12: Air Ducts

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions There are no provisions for an internal filter rack in these furnaces. A supply-air duct must be connected to ONLY the factory-approved field-supplied accessory external filter rack is required. accessory subbase, or a factory-approved air conditioning coil casing.
  • Page 13 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions A02163 Fig. 18 – Downflow Return Air Configurations and Restrictions A190054 Fig. 19 – Upflow Return Air Configurations and Restrictions A02162 Fig. 20 – Horizontal Return Air Configurations and Restrictions Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 14: Gas Piping

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions GAS PIPING CAUTION Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC in the U.S. FURNACE DAMAGE HAZARD Installations must be made in accordance with all authorities having Failure to follow this caution may result in furnace damage.
  • Page 15: Electrical Connections

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Field-supplied wiring shall conform with the limitations of 63°F (33°C) rise. WARNING ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings could result in dangerous operation, serious injury, death or property damage.
  • Page 16: J-Box Relocation

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Table 5 – Electrical Data OPERATING VOLTAGE VOLTS - MAX WIRE MAX. FUSE MAX. UNIT UNIT MIN. WIRE RANGE FURNACE SIZE HERTZ - LENGTH OR CKT. † AMPS AMPACITY GAUGE ‡...
  • Page 17 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Electrical Connection to J-Box 3. Secure power cord to J-Box bracket with a strain relief bushing or a connector approved for the type of cord used. Electrical Box on Furnace Casing Side 4.
  • Page 18 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions A03179 Fig. 29 – Two-Stage Furnace with Two-Speed Air Conditioner A03178 Fig. 31 – Two-Stage Furnace with Two-Speed Heat Pump (Dual Fuel) A03180 Fig. 30 – Two-Stage Furnace with Single-Speed Heat Pump...
  • Page 19: Notes For Figures 28 - Figures 35

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions A03184 Fig. 35 – Single-Stage Thermostat with Two-Stage Furnace and A03182 Fig. 33 – Dual-Fuel Thermostat with Two-Stage Furnace and Two-Speed Air Conditioner Two-Speed Heat Pump NOTES FOR FIGURES 28 - FIGURES 35: 1.
  • Page 20: Accessories

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions ACCESSORIES (if used) to the 1/4-in male quick-connect HUM terminal and COM-24V screw terminal on the control board thermostat strip. 1. Electronic Air Cleaner (EAC) The HUM terminal is energized when blower is energized in Connect an accessory Electronic Air Cleaner (if used) using 1/4-in heating.
  • Page 21 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions the furnace and the FAN-Max vent connector capacity is equal to or higher than the furnace high fire rate. 3. Do not vent this Category I furnace into a single wall dedicated or common vent.
  • Page 22: In Thousands Of Btuh Per Hour

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions 1. Vent connector is Type-B double-wall, and Table 7 – Minimum Allowable Input Rating of 2. This furnace is common vented with at least 1 draft hood equipped Space-Heating Appliance in Thousands of Btuh per Hour...
  • Page 23 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions CAUTION CAUTION BURN HAZARD CUT HAZARD Failure to follow this caution may result in personal injury. Failure to follow this caution may result in personal injury. Hot vent pipe is within reach of small children when installed in Sheet metal parts may have sharp edges or burrs.
  • Page 24 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions A03210 Fig. 41 – Downflow Application - Vent Elbow Up then Left A03208 Fig. 38 – Upflow Application - Vent Elbow Up A03211 Fig. 42 – Downflow Application - Vent Elbow Up A03209 Fig.
  • Page 25 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions A03215 Fig. 47 – Horizontal Left Application - Vent Elbow Up A03207 Fig. 44 – Downflow Application - Vent Elbow Left then Up A03216 Fig. 48 – Horizontal Left Application - Vent Elbow Right A03212 Fig.
  • Page 26: Start-Up, Adjustment, And Safety Check

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Venting Notes for Fig. 38 Fig. 50 5. Replace blower compartment door. Door must be in place to operate furnace. 1. For common vent, vent connector sizing and vent material: United 6.
  • Page 27: Adjustments

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions ADJUSTMENTS b. Obtain average yearly gas specific gravity from local gas supplier. WARNING c. Find installation altitude in Table d. Find closest natural gas heat value and specific gravity in Table FIRE HAZARD e.
  • Page 28 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions c. When correct input is obtained, replace caps that conceal gas high-heat operation, place setup switch SW1-2 in OFF position and valve regulator adjustment screws. Main burner flame should be jumper R-W2 on furnace control. DO NOT forget to return setup switch clear blue, almost transparent.
  • Page 29 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions The thermostat anticipator should NOT be in the circuit while Table 10 – Gas Rate (CU ft./hr) measuring current. SIZE OF TEST (1.) Set SW1-2 switch on furnace control board to ON.
  • Page 30 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Table 11 – Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate (Tabulated Data Based on 22,000 Btuh High-Heat/14,500 Btuh for Low-Heat per Burner, Derated 4 Percent for Each 1000 Ft.(305 M) Above Sea Level) SPECIFIC GRAVITY OF NATURAL GAS 0.58...
  • Page 31 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Table 11 – Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate (Tabulated Data Based on 22,000 Btuh High-Heat/14,500 Btuh for Low-Heat per Burner, Derated 4 Percent for Each 1000 Ft.(305 M) Above Sea Level) (Continued) SPECIFIC GRAVITY OF NATURAL GAS AVG.
  • Page 32 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions A190047 Fig. 53 – Service Label A190048 Fig. 54 – Furnace Setup Switch Description A190049 Fig. 55 – Airflow Selection (based on 350 CFM/TON) for A/C (SW2-6, 7, 8) and *CF (SW2-3, 4, 5)
  • Page 33 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Table 12 – Air Delivery - CFM (With Filter)* COOLING AND HEATING AIR DELIVERY - CFM (Bottom Return With Filter) (SW1-5 and SW2-2 set to OFF, except as indicated. See Notes 1 and 2.)
  • Page 34 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Table 12 – Air Delivery - CFM (With Filter)* (Continued) COOLING AND HEATING AIR DELIVERY - CFM (Bottom Return With Filter) (SW1-5 and SW2-2 set to OFF, except as indicated. See Notes 1 and 2.)
  • Page 35 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Table 12 – Air Delivery - CFM (With Filter)* (Continued) COOLING AND HEATING AIR DELIVERY - CFM (Bottom Return With Filter) (SW1-5 and SW2-2 set to OFF, except as indicated. See Notes 1 and 2.)
  • Page 36: Service And Maintenance Procedures

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions Table 12 – Air Delivery - CFM (With Filter)* (Continued) COOLING AND HEATING AIR DELIVERY - CFM (Bottom Return With Filter) (SW1-5 and SW2-2 set to OFF, except as indicated. See Notes 1 and 2.)
  • Page 37: General

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions interrupted. The control will store up to the last 7 Status Codes in order WARNING of occurrence. NOTE: NO thermostat signal may be present at control, and all ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD blower-OFF delays must be completed.
  • Page 38: Care And Maintenance

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions 5. Inspect the vent pipe/vent system before each heating season for WARNING rust, corrosion, water leakage, sagging pipes or broken fittings. Have vent pipes/vent system serviced by a qualified service agency.
  • Page 39 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions WARNING WARNING ELECTRICAL SHOCK HAZARD ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Failure to follow this warning could result in personal injury, or death.
  • Page 40 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions 6. Remove screws that fasten the collector box assembly to the cell (3.) Work cable in and out of cell 3 or 4 times to obtain panel. Be careful not to damage the collector box. Inducer assembly sufficient cleaning.
  • Page 41: Sequence Of Operation

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions SEQUENCE OF OPERATION until the high-heat pressure switch closes for a maximum of 2 minutes after ignition. NOTE: Furnace control must be grounded for proper operation or else b. Igniter Warm-Up -At the end of the prepurge period, the control will lock out.
  • Page 42 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions 2. Two-Stage Thermostat and Two-Stage Heating The furnace control CPU can start up the cooling unit in either low- or Fig. 28 Fig. 35 for thermostat connections high-cooling. If starting up in low-cooling, the furnace control CPU...
  • Page 43 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions non-Thermidistat mode. is stored in the memory to be automatically used following a power The cooling operation described in item 3. above also applies to interruption. operation with a Thermidistat. The exceptions are listed below: NOTE: If the blower-off delay is set to the maximum, the adjustable a.
  • Page 44: Wiring Diagram

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions WIRING DIAGRAM A210177 Fig. 59 – Wiring Diagram Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 45: Troubleshooting Guide

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions TROUBLESHOOTING GUIDE A14311A Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 46 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions A14311B Fig. 60 – Troubleshooting Guide Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 47: Parts Replacement Information Guide

    58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions PARTS REPLACEMENT INFORMATION GUIDE Burner assembly CASING GROUP Orifice Flame sensor Outer door Hot surface igniter Blower door Gas valve Top filler plate Manual reset limit switches Bottom filler plate Burner support assembly...
  • Page 48 58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions © 2021 Carrier. All rights reserved. Edition Date: 08/21 Catalog No: 58TP0A-03SI REV A Replaces:58TP0A-03SI Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

This manual is also suitable for:

58tp0aA series

Table of Contents