Setting Sensor Parameters - Huawei TP48200A-HT19C4-1 Installation Manual

Hide thumbs Also See for TP48200A-HT19C4-1:
Table of Contents

Advertisement

TP48200A-HT19C4-1 & TBC300A-TCA2
Installation Guide
Table 10-2 Setting battery parameters
Main
Menu
Parameters
Settings

10.5 Setting Sensor Parameters

Set the sensor parameter to Yes or None based on actual sensor configurations.
shows the LCD menus and parameter settings.
Issue 01 (2014-03-12)
Second-
Level
Menu
Battery
If battery routes 1 and 2 are respectively connected to a battery string (each battery string consists of
four 12 V, 150 Ah batteries in series), set Battery1 Connected and Battery2 Connected to Yes and
others to No, and set Rated Capacity to 150 Ah.
If battery route 1 is connected to two battery strings in parallel (each battery string consists of four
12 V, 150 Ah batteries in series), set Battery1 Connected to Yes and others to No, and set Rated
Capacity to 300 Ah.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Third-
Fourth-
Level
Level
Menu
Menu
Basic
Battery 1
Parameters
Connected
Battery 2
Connected
Rated
Capacity
Other
Installatio
Parameters
n Time
10 Commissioning
Default Value
Setting Value
Yes
If N battery
strings are
connected, set
Yes
Battery 1
Connected to
Battery N
Connected to
Yes, and set the
other
parameters to
No.
150 Ah
Rated capacity
of the batteries
in a battery
string.
NOTE
The batteries
controlled by
one circuit
breaker or fuse
are called a
battery string.
-
Set to the
current date
Table 10-3
74

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tbc300a-tca2

Table of Contents