Service Manual Page 1 Pro3V120 This manual is valid for XT series drives revisions 5.9A. The parameter numbers are based on the software version Pro3V120. CAUTION Before starting, read the instructions carefully. Verify all of the connections are in done in accordance to the drawings.
Closed Loop manual tuning for hoisting, speed control ----------------------------------- 4.5.4 Brake Control -------------------------------------------------------------------------------------- Brake Slip feature ---------------------------------------------------------------------------------------- 4.6.1 Description of brake slip feature --------------------------------------------------------------- Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 4
XT Series Quick Setup Guide (Open Loop Hoist) ------------------------------------------------ WIRING DIAGRAMS ------------------------------------------------------------------------------------------ 98 • CONTROL UNIT CONNECTIONS ---------------------------------------------------- Inside Back Cover Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
AIN1: 0 … +10V and AIN2: -10 … +10V; 200k load ; accuracy 0.5% Encoder feedback EA+/- and EB+/-; 0/24V; 3k load; floating differential inputs Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 6
Maximum 1000m at In. Above 1000m: In reduces 1% per each 100m. Above 3000m: consult factory. Vibration Operation: maximum displacement amplitude 1mm at 3-15.8Hz. Maximum acceleration amplitude 1G (9.81m/s²) at 15.8-150Hz Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Pro3V120 Type mark coding XT Series drives can be summarized as "crane motor control systems, which controls the speed by changing the frequency of the supply voltage of a squirrel cage motor". A stepless speed adjustment can be achieved by this method. Type marking is shown below.
Page 7 Pro3V120 Basic description XT Series drives have many advantages and offer many new features, when compared to other inverter based systems, which might be used in crane applications. Inverter The XT Series drive is a crane specific inverter. The specific crane...
This amplifier should be located as close to the motor as possible. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
AP = 1 DIA3 AP = 0 AP = 1 DIA4 CMS not used CMS not used CMS = 0 CMS = 0 Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 11
Service Manual Page 10 Pro3V120 If required, two or more XT Series drives can be run in precise digital Synchronization synchronization. A separate synchronization controller is needed for this. The same speed reference (in EP- or PO-mode) and the correction signal are connected to each drive.
Also, different applications may require this brake to be used differently. As a default, XT Series drive panels are wired to control a single-phase AC brake. If a 3-phase brake is to be used, some wiring changes will be required. If a DC brake is being used, a brake rectifier will need to be used.
Motor control modes Open loop XT Series drives have a built-in motor model, which calculates - one thousand times per second - the values of the motor. The input data needed for the calculation is the instantaneous value of the motor voltage from the ASIC and the measured motor current.
The XT Series drives used in North America have this filtering capacity modified to allow for the varying types and fluctuations in the power network. If the European Union EMC standards are necessary, the power supply must meet minimum requirements and the drive configuration for this must be specified when ordering.
The first environment is divided in to categories C1 and C2. XT Series drives are not intended to be used on a low-voltage public network, which supplies domestic premises. The drive may cause radio frequency interference to other devices if used on such a network.
Cooling The cooling requirements for XT Series drives vary by application. The actual thermal loading of the enclosure has to be estimated based on the environmental conditions and duty cycles. The power losses of the drive are listed in the below table for each power rating in units of Watts [W].
Motor cable Braking resistor cable for hoist CMAA Class D SRML Cable Braking resistor cable for travel CMAA Class D SRML Cable Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
The cable for bearing sensors or pulse sensors must be shielded round sensor cable and should be 360° grounded at both ends. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
D2V. The D2V units are suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 600V maximum. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
- Make sure that the external connections and programming of the digital and analog inputs are done according to the application requirements. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
- Copy all parameters up to keypad memory at parameter 6.3.2. - Save user parameters in Control Unit at parameter 4.1.2. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Move cursor right Decrease values Enter edit mode Warning! Running via keypad can cause a hazardous situation. Keypad control must not be used. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
400 V enter Warning! Changing parameter settings during running may cause a hazardous situation. Parameter settings must not be changed during operation. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
“All Parameters” is flashing. Now press “Enter” on the keypad and wait until the keypad says “OK” **Verify that parameters have correctly loaded by comparing loaded parameters with recorded parameters Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
V4.6.25 Ramp Reference V4.6.26 Torgue Limit Ref V4.6.27 Speed Limit Ref V4.6.28 Load Feedback V4.6.29 Sway Ctrl Height V4.6.30 Calibration Pos Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Multistep3 P3.2.1.14 Multistep4 P3.2.1.15 Multistep5 P3.2.1.16 PO/MS P3.2.1.17 P3.2.1.18 P3.2.1.19 S11 & S21 P3.2.1.20 P3.2.1.21 P3.2.1.22 MF1 Input P3.2.1.24 MF2 Input Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Brake Slip (A84): Active only when the parameters have been programmed for this detection. See section 4.6 of this manual for further information about this feature. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 28
S2:4, together with S3, are used for setting the tripping frequency level at ESR speed. If ESR is not used, set S2:4 + S3 equal to S2:1 and S1. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Set rotary switch S1/S3 back to its original value. Note! The test makes the crane stop suddenly that may cause a dangerous situation. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Maximum Frequency S1 Set equal to desired maximum frequency (usually the P3.4.1.16 Maximum Frequency S2 nominal frequency on motor rating plate). Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
- A simple multimeter might not be good enough to measure low resistances. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
- Motor nominal current must not be higher than drive’s rated current. - The number of connected motors must not be variable. 1. P3.4.1.9 Control Mode Set to 1 (OL Current Control). Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Control Mode Verify the value is 3 (CL Speed Control). Note! Check the operation of limit switches before performing closed loop tuning. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 34
Closed loop speed control is very sensitive to encoder pulse defects. Faulty encoder connections and/or disturbance in encoder pulses may cause wrong operation or inverter faults. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
- Check value of P3.4.3.1 Slip Adjust. If the value is very close to 200, reset the value to 70 and continue to autotuning step 2 Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 36
- Drive upwards or forwards (dir 1), accelerate straight to full speed and stop driving. - Fine-tuning may require several driving operations. - If autotuning fails, check instructions from troubleshooting section. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 37
If autotuning does not give a proper result, go through chapter 4.5.3. Closed Loop manual tuning for hoisting, speed control. In case of traveling motion, contact factory for more information. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
380 V 400 V 415 V 440 V 460 V 480 V 500 V V4.18 Lower Limit Voltage V4.18 Upper Limit Voltage Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
The drive is ready to operate after these manual-tuning adjustments. If there is any vibration, fine adjustment of speed controller parameters may improve the operation. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 40
V4.22 V4.20 Motor Voltage Output Frequency Motor Current Speed Controller Record values of P3.4.3.3 P3.4.3.4 Speed Ctrl Kp Speed Ctrl Ti Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Drive tuning, external electrical drive connections, and encoder installation/quality/coupling to the motor are key factors for this feature to work precisely. Consult above warning label. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
- All precautionary safety measures should be taken as in any crane load testing. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 43
Wait for 5 minutes then power up crane and check that hoist function is normal. Contact Drivecon technical support for assistance if required at 1-800-374-8266. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Power should be turned off/crane tagged and locked prior to any service being performed on the crane. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
G3.5.3 Bus Control G3.6 Protection G3.7 Laboratory + G3.8 System Bus G3.8.7 Synchronization G3.8.7.5 Monitoring G3.8.8 Tandem + G3.9 PLC Parameters Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 46
S6.8.3 Software S6.8.4 Applications S6.8.5 Hardware S6.8.6 Expander boards S6.8.7 Debug S6.9 Power Monitor S6.11 Power Multimon. Active Faults Fault History Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 47
4 = DIA4 P3.2.1.21 0 = Not Used 1 = DID5 2 = DID3 & DID5 3 = DIA4 4 = DIA5 Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 48
0 = 0-20mA Sign 1 = 4-20mA Sign 2 = 0-20mA Unsig 3 = 4-20mA Unsig P3.2.4.1.5 Aout1 FilterTime 0.10 0.10 0.10 0.10 Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 49
3 = Form 3 4 = Form 4 V3.3.8.4 Dec TotalRamp Time P3.3.8.5 Stop Ramp S1 P3.3.8.6 Stop Ramp S2 P3.3.8.7 Direction Change Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 50
Dir Change Limit P3.3.15.10 Max Height 40.00 40.00 40.00 40.00 P3.3.15.11 Load Ratio P3.3.15.12 License Key 1 P3.3.15.13 License Key 2 Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 51
0 = MotorNomFreq 1 = Max Freq S1 2 = MaxFreqS1+PD P3.4.1.21.12 Accel Torque P3.4.1.21.13 Power Limit Mot P3.4.1.21.14 Power Limit Gen Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 52
2 = Restart Dir1 3 = LoadTooSmall 4 = SlipAdjFault 5 = StoreFailure 6 = Failed 7 = Done 9 = Stop Driv ing Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 53
PW 4 Description P3.4.4.23.1 Current Ctrl Kp 4000 4000 4000 4000 P3.4.4.23.2 Current Ctrl Ti P3.4.4.23.3 Accel Comp TC 0.10 0.10 0.10 0.10 Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 54
8 = Modif ied 9 = Stop Driv ing P3.4.6.6.5 SlipAdj2 Ctrl TC B3.4.6.6.6 CL Autotune Mode 0 = Normal 1 = Tandem Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 55
P3.5.2.4 Process Data 6 Same as P3.5.2.1 P3.5.2.5 Process Data 7 Same as P3.5.2.1 P3.5.2.6 Process Data 8 Same as P3.5.2.1 Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 56
6 = 2.5 kHz P3.6.8 Brake Slip 0 = Not Used 1 = S1 Allowed 2 = S1 Slow Spd 3 = S1 Disabled Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 57
11 = D/A BoardCh1 12 = D/A BoardCh2 P3.7.19.7 Condition 2 0 = > 1 = >= P3.7.19.8 Limit 2 V3.7.19.9 Data Log Counter Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 58
PLC Parameters OL Trav CL Trav CL Hoist OL Hoist Unit PW 3 Description P3.9.1 PLC Parameter 1 P3.9.2 PLC Parameter 2 Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
530x1350x362 20.87x53.15x14.25 e defines the power supply network (0 = unlimited or IT network, N = limited or grounded Y network) Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 60
XTx2140NJ1e04 PSU037NJ1e1 CSU04 288x758x344 11.34x29.84x13.54 XTx2170NJ1e04 PSU045NJ1e1 CSU04 288x758x344 11.34x29.84x13.54 e defines supply network ( 0 = unlimited, N = limited) Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 61
The main circuit diagram of XTx4031 – XTx4245 and XTx5027 – XTx5170 UH_G VH_G WH_G UH_D VH_D WH_D U/T1 V/T2 W/T3 UL_G VL_G WL_G BRK_G VL_D WL_D UL_D BRK_D Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
NOT running blinking IEC Application Scheduler 0.5Hz and Application are NOT running Green Status YELLOW PSU ready PSU not ready Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
OK is 35VAC, 15mA. 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Status Yellow 0.25Hz Yellow Board internal fault or communication fault with control unit 1 2 3 4 5 6 28 29 Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Relay output, 250V 8A, ROE3 normal open ROE3 Blinking Status Yellow 0.25Hz Yellow Board internal fault or communication fault with control unit Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
- no messages from Profibus master within the watchdog time - Profibus cable broken, cable loose or Profibus master off line Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Drive 3 / Follower Drive 4 / Follower H4/Tx2 H1/Rx1 H4/Tx2 H1/Rx1 H4/Tx2 H1/Rx1 H4/Tx2 H1/Rx1 H2/Rx2 H3/Tx1 H2/Rx2 H3/Tx1 H2/Rx2 H3/Tx1 H2/Rx2 H3/Tx1 Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Service Manual Page 67 Pro3V120 Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Pro3V120 Reference potentiometer A special potentiometer connection is used with the XT Series drive. End terminals of the potentiometer are shorted together and connected to the +10V terminal which is on the A board pin #5. The power supply is connected via a series resistor to the A board pin #1. The wiper of the potentiometer must be connected to the A board pin #3.
6.3.1 Encoder An incremental encoder can be used with XT Series drives to obtain excellent speed accuracy and fast response as well as to reach very low minimum speeds for precise positioning. The encoder signal is also used for speed supervision purposes. Standard encoder has 600 pulses per revolution. The XT is allowed to use 512, 1000, 1024, 1200, 2000 or 2048 ppr encoders depending on motor speed and cable length.
- grounded (the shield) at both ends, 360 degree grounding on the drive terminal the shield should be grounded always when going through terminals Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
The speed supervision sensor connection to the buffer amplifier KAE248 is performed as follows: Brown Brown + 24V Green Green Black Black White Blue Schönbuch INSOR ICDM 8802 Baumer IFRM08N1501/L Honeywell 3GT101DC Baumer IFRM08N1501/S35L Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
24V± 1V Buffer amplifier pulse output can be measured during running. The picture on the right presents the pulse output. 0± 1V Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
DC-circuit, which speeds closing of the brake. The purpose of the varistor is to provide overvoltage protection for K7 contacts and the brake coil. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
If parameters have been copied to the keypad before damage, it may be used for uploading the parameters to the spare or replacement inverter (requires same software versions). Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
XT series drives include an automatic fault reset operation; the fault code stays on the display until the fault is removed and the controller released back to 0-position. Some of the fault codes require to switch the power off before run is possible.
Page 77
• if there is a system bus board in the D2V, replace the board • replace other boards in Slots D or E • replace the control unit Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 78
• component failure (control unit) Microprocessor contact authorized service. watchdog-fault F 26 Faulty power unit Contact authorized service. Power Unit Fault Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 79
Poor Profibus cable connection or communication Check: problems with Profibus master. • Profibus slave address • Profibus cable connection • Profibus termination resistor settings Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 80
Brake is opening or closing in wrong time Check: Brake Feedback • brake operation Fault • brake relay (ROB2) and brake contactor (K7/K71) operation Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
0=Not Ready 1=Ready T.10 0=Not Running 1=Run T.11 Direction 0=Off 1=On Fault 0=No 1=Yes T.12 Warning 0=No 1=Yes At reference 0=No 1=Yes Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
F35, F36, F37, F38, F39, F40, F44, F45, F48, F50, F54, F55, F60, F64, F65, F71, F72, F73, F75 V4.5.25 Total Faults Total number of all faults. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
One or both Sway Control License Check: SwCtrlLicens Keys are incorrect or missing - License Key numbers - Sway Control mode Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Service Manual Page 83 Pro3V120 SERVICE In the normal operation XT Series drives do not require regular maintenance. The following actions are recommended: Check the fault history of the inverter - Find out reasons of possible faults - Record faults and clear the fault history...
Service Manual Page 84 Pro3V120 QUICK SETUP GUIDES See following pages Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
(Set to nameplate value) 3.4.1.16 - Max. Freq. S2 (Set to nameplate value) 3.4.1.20 - PPR (Must be set according to proper encoder/sensor value) Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 87
“Done.” If at any time during this step you need to drive in the down direction to make more room, you can do so without causing Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 88
If you want to return to the multimonitor screen, which displays motor voltage, motor current, and output frequency, navigate to parameter 4.23.1. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 89
Motor torque **Copy parameters to or from keypad G4.23 Multimonitor System Menu S6.3 Copy Parameters S6.4 Parameter comparison Active Faults Fault History Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
(Set to 120% of 3.4.1.4) 3.4.1.15 - Max. Freq. S1 (Set to nameplate value) 3.4.1.16 - Max. Freq. S2 (Set to nameplate value) Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 91
If you want to return to the multimonitor screen, which displays motor voltage, motor current, and output frequency, navigate to parameter 4.23.1. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 92
Multimonitor **Default display System Menu S6.3 Copy Parameters **Copy parameters to or from keypad S6.4 Parameter comparison Active Faults Fault History Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
(If not available, set at 50% of motor rated current) 3.4.1.6 - Motor [Cos Φ] (= Motor Power Factor. If not available, do not change) Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 94
6.3.2 and upload the drive parameters to the keypad. Doing so causes your programmed parameters to be saved to the internal memory inside the drive’s keypad. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 95
Multimonitor **Default display System Menu **Copy parameters to or from keypad S6.3 Copy Parameters S6.4 Parameter comparison Active Faults Fault History Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
5. Verify the follow parameters are set accordingly: 3.4.1.9 - Control Mode (Set for OL Frequency Control) 3.4.1.10 - Accel Time 1 (Set for 1.5 seconds) Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 97
6.3.2 and upload the drive parameters to the keypad. Doing so causes your programmed parameters to be saved to the internal memory inside the drive’s keypad. Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Page 98
Motor torque G4.23 Multimonitor **Copy parameters to or from keypad System Menu S6.3 Copy Parameters S6.4 Parameter comparison Active Faults Fault History Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...
Service Manual Page 98 Pro3V120 WIRING DIAGRAMS See following pages Drivecon reserves the right to alter or amend the above information without notice. 11/22/11 • rev 5.9A for Pro3V120...