INSTALLATION INSTRUCTIONS: BRIZA12 - WALL AND CEILING

Advertisement

Table of Contents
loading

Summary of Contents for Jaga BRIZA 12 Series

  • Page 1 BRIZA 12: STAND ALONE / BUILT-IN INSTALLATION INSTRUCTIONS: BRIZA12 - WALL AND CEILING...
  • Page 2: Table Of Contents

    12. MAINTENANCE ......................21 13. WARRANTY ....................... 22 14. DISSASSEMBLY INSTRUCTIONS ............... 22 DECLARATION OF CONFORMITY JAGA N.V. - Verbindingslaan 16 - B 3590, declares under its sole responsibility that the CEO JAGA N.V. product to which this declaration relates: BRIZA 12, BRIZA 22...
  • Page 3: Used Symbols

    1.  USED SYMBOLS the DANGER sign warns the operator and maintenance staff about risks that may cause death, physical injury or illnesses of any kind. DANGER: ELECTRICAL HAZARD DANGER: SHARP EDGES DANGER: HOT SURFACES DANGER: MOVING PARTS ATTENTION: IMPORTANT WARNING the ENVIROMENTAL SAFEGUARD sign provides instructions on how to use the unit in an ECO-friendly manner.
  • Page 4: Warnings And Safety

    2.  WARNINGS AND SAFETY Handling guidelines: The unit must be handled with care in order to avoid damage to the unit’s interior and exterior parts. The unit might have sharp edges; use gloves during installation/adjustment. All the operations listed below must be carried out in accordance with local health and safety regula- tions.
  • Page 5: General Information

    –  bleed the air from the hydronic system. –  it is advisable to run the unit at maximum speed and to check for abnormalities. Device description: Jaga Briza 12 are fan coils for the treatment of air in indoor environments. maximal water temperature: 195°F. test pressure: 377PSI...
  • Page 6: Product Description

    6. PRODUCT DESCRIPTION 6.1. CEILING Dynamic Low-H2O hydrophilic coated coil Hydraulic connection 2-pipe 3/4 NPT Dynamic outlet grille* Secondary drain pan (Option for ceiling built-in) Condensate drain pan (ceiling built-in) Electrical connection The direction of the air flow is determined by the position of the grill. Install the grill with deflection into the room direction.
  • Page 7: Technical Data

    7.  TECHNICAL DATA 7.1.  DIMENSIONS WALL MOUNTED MODEL 7.1.1.  Installation in a wall recess : Briza 038 / Briza 052 4 ³⁹/₆₄ 2 ⁷/₈ 3 ¹⁵/₆₄ 1 ²⁷/₆₄ 1 ⁴⁷/₆₄ 4 ³⁹/₆₄ 3 ⁷/₆₄ 2 ⁷/₈ L - 0 ⁶³/₆₄ 1 ⁷/₆₄...
  • Page 8 7.2.  DIMENSIONS CEILING-MOUNTED-MODEL 7.2.1.  Built-in ceiling : Briza 038 / Briza 052 1 ⁴⁹/₆₄ 1 ¹/₂ 3 ⁵/₆₄ min. 2 ⁷/₈ min. 4 ⁵⁹/₆₄ 4 ⁵⁹/₆₄ 5 ²⁹/₃₂ 5 ²⁹/₃₂ 9 ²⁷/₃₂ 9 ²⁷/₃₂ min. min. min. min. 5 ²⁹/₃₂ 5 ²⁹/₃₂...
  • Page 9: Operating Limits

    8. OPERATING LIMITS If the fancoil unit is supplied with chilled water, condensate from the coil will be drained via the con- densate drain connection. At water temperatures below dewpoint, condensation may occur on components other than the coil. This is not collected in the condensate drain, and might drip from under the unit. Therefore the supply, return and drain pipes must be insulated.
  • Page 10 Remove the screws above and below the unit. Remove the enclosure. Mark the screw holes, use the unit as a template or according to The type of wall determines what type of screw or plug should be the dimensions specified on page 8 and 10 in this guide. used.
  • Page 11 1” per 3ft 1” per 3ft Wall Ceiling Setting up the condensate drain: The condensate drain pipe must be installed with an adequate slope to make sure the water drains properly. The supply and return pipes for chilled water and their valves must be insulated against condensati- OPTION: secondary drain pan for Briza Built-In Ceiling BRIZA H38: ref.
  • Page 12 9.2. ELECTRICAL CONNECTION IMPORTANT! The electrical connection of the unit must be carried out by a certified technician , in compliance with the local building codes. Non-conforming electrical connections releases Jaga N.V. from liability concerning damage to objects and persons. DANGER! – ...
  • Page 13 9.2.1. Option: Electrical connection - 0...10V It is important to have a common ground Briza +24 V on all power supplies used for power and 0...10 V control signal (for example from BMS or thermostat with speed control). + 0...10V 0..10V CODE: 7990.050/51/52 Power supply DC LO...
  • Page 14: Initial Start

    10.  INITIAL START IMPORTANT! Start-up and Commissioning of the fancoil must be carried out by skilled staff, qualified to work on this type of product. DANGER! Before start-up, make sure the installation has been carried out in compliance with in this manual. Before start-up the fancoil unit, check if: 1.
  • Page 15 11.2.  ROUTINE MAINTENANCE Every 6 months: Check the condition of the coil and condensate drain: If necessary: –  remove any dirt from the coil surface –  remove dust using an air compressor –  wash with water and brush gently –  dry by using compressed air – ...
  • Page 16: Warranty

    –  the fan coil has not been periodically cleaned, –  the unit has been used in an improper or irresponsible manner, –  repairs have been carried out by others than Jaga, –  product modifications have been carried out by others, before or after the installation, – ...