W/r410a single package gas-electric heating & cooling unit
Hide thumbs Also See for APG14 M Series:

Advertisement

O
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL
(
, "
REPAIR
HEREINAFTER
SERVICE
MANUAL SHOULD SERVICE THE EQUIPMENT
BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM
IMPROPER SERVICE OR SERVICE PROCEDURES
ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY
. I
,
RESULT
N ADDITION
IN JURISDICTIONS THAT REQUIRE ONE OR MORE
LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL
LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT
,
,
INSTALLATION
ADJUSTMENT
SERVICING OR REPAIR OF THE EQUIPMENT
,
SPECIFIED IN THIS MANUAL
OR ATTEMPTING TO INSTALL
REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER
TRAINING MAY RESULT IN PRODUCT DAMAGE
.
INJURY OR DEATH
IOG-3008H
06/2019
INSTALLATION & OPERATING
INSTRUCTIONS for
A/GPG14 M SERIES W/R410A
SINGLE PACKAGE GAS-ELECTRIC
HEATING & COOLING UNIT
Affix this manual and Users Information Manual adjacent to the unit.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
,
,
ADJUST
")
THE EQUIPMENT SPECIFIED IN THIS
. T
HE MANUFACTURER WILL NOT
. I
F YOU SERVICE THIS UNIT
. I
MPROPER
,
ADJUST
,
PROPERTY DAMAGE
Goodman Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com - or - www.amana-hac.com
2014-2019 Goodman Company, L.P.
©
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
These installation instructions cover the outdoor
installation of single package gas electric heating and
cooling units. See the Specification Sheet or Technical
SERVICE OR
Manual applicable to your model* for information
regarding accessories.
*NOTE: Please contact your distributor or our
,
YOU
Sheet or Technical Manual referred to in this
,
ONLY
,
SERVICE OR
,
PERSONAL
This Forced Air Central Unit Design Complies With
Requirements Embodied in The American National
Standard / National Standard of Canada Shown Below.
ANSI Z21.47•CSA-2.3 Central Furnaces
website for the applicable Specification
manual.
PROP 65 WARNING
FOR CALIFORNIA CONSUMERS
Cancer and Reproductive Harm
www.P65Warnings.ca.gov
-
0140M00517-A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the APG14 M Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Amana APG14 M Series

  • Page 1 Goodman Company, L.P. IOG-3008H 5151 San Felipe, Suite 500, Houston, TX 77056 06/2019 www.goodmanmfg.com - or - www.amana-hac.com 2014-2019 Goodman Company, L.P. © is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
  • Page 2: Table Of Contents

    Index Replacement Parts ....................................3 ..................................... 3 RDERING ARTS Safety Instructions ....................................3 General Information ....................................6 ..................................6 RANSPORTATION AMAGE Unit location ....................................... 7 : ....................................7 NSTALLATIONS : ................................7 ROUND EVEL NSTALLATIONS : ..................................7 OOFTOP NSTALLATIONS : ................................
  • Page 3: Replacement Parts

    REPLACEMENT PARTS RDERING ARTS When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate. Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact: HOMEOWNER SUPPORT...
  • Page 4 AVERTISSEMENT CARBON MONOXIDE POISONING HAZARD RISQUE D'INTOXICATION AU MONOXYDE DE CARBONE Failure to follow the steps outlined below for each Si les étapes décrites ci-dessous ne sont pas suivies pour appliance connected to the venting system being placed chacun des appareils raccordés au système de ventilation into operation could result in carbon monoxide poisoning au moment de sa mise en marche, cela peut entraîner une or death.
  • Page 5 FIRE OR EXPLOSION HAZARD CARBON MONOXIDE POISONING HAZARD Failure to follow instructions could result in severe personal Failure to follow the safety warnings exactly could result in injury or death due to carbon-monoxide poisoning, if serious injury, death or property damage. combustion products infiltrate into the building.
  • Page 6: General Information

    Goodman brand prod- 3. In case of concealed damage, carrier should be notified ® ucts or www.amana-hac.com for Amana brand products. Within as soon as possible-preferably within 5 days. either website, please select the residential or commercial prod- 4.
  • Page 7: Unit Location

    UNIT LOCATIONS • The top of the unit should be completely unobstructed. If units are to be located under an overhang, there should be a minimum of 48” clearance and provisions made to WARNING deflect the warm discharge air out from the overhang. O PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT.
  • Page 8: Roof Curb Installations Only

    NSTALLATIONS • Sufficient structural support must be determined prior to locating and mounting the curb and package unit. • Ductwork must be constructed using industry guidelines. The duct work must be placed into the roof curb before mounting the package unit. •...
  • Page 9: Piping

    Refer to the Installation Manual provided with the LP kit for conver- • Listed gas appliance connectors used in accordance sion from natural gas to propane gas and for altitude adjustments. with the terms of their listing that are completely in the NOTE: Up to 2,000 feet, no changes are required;...
  • Page 10: Propane Gas Installations

    flame in the vicinity during air bleeding procedure. The unit is Sizing Between First and Second Stage Regulator Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10 placed in operation by closing the main electrical disconnect PSIG Setting.
  • Page 11: Ingle Tage Hermostat

    etc. Consult the Instruction Sheet packaged with thermostat INGLE TAGE HERMOSTAT TAGE ODELS for mounting instructions. To use a single stage thermostat, move jumper located to the Five ton models have two stages of heating and two stages of left of the terminal strip labeled “Stage Delay” from NONE to mechanical cooling.
  • Page 12: Unit Voltage

    Note:Junction box location shown is optional and is for illustration purposes only. JUNCTION BOX Remove these covers for horizontal duct applications Electrical Power Directly To Junction Box Electrical Power Routed Through Bottom of Unit Typical Electrical Wiring Unit Voltage Duct Cover Installation OLTAGE Down Discharge Applications The unit transformer is factory connected for 230V operation.
  • Page 13: Filters

    The supply duct from the unit through a wall may be installed without clearance. However, minimum unit clearances as shown in the appendix must be maintained. The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger. A cover should be tightly attached to prevent air leaks.
  • Page 14: Cooling

    5 seconds after the main burners light. If call is for high stage heat, induced draft blower remains at high speed 1. Thermostat calls for FAN ONLY by energizing “G”. and high stage gas valve remains open. 2. Approximately seven seconds later, the indoor fan starts. NOTE: If a single stage thermostat is used, the control will step to low stage after the main burners light and remain Two-Stage Models:...
  • Page 15: As Upply Ressure Easurement

    Secondary Limit Control The secondary limit control is located on the top of the blower scroll assembly. This control opens when elevated INLET OUTLET temperatures are sensed. Elevated temperatures at the control are normally caused by blower failure. The reason for the opening should be determined and repaired prior to resetting.
  • Page 16 High Fire Regulator Adjust Outlet Regulator Pressure Boss Vent Low Fire The line pressure supplied to the gas valve must be within the Regulator Adjust range specified in the Inlet Gas Supply Pressure table. The supply pressure can be measured at the gas valve inlet pressure tap or at Inlet a hose fitting installed in the gas piping drip leg.
  • Page 17: Gas Manifold Pressure Measurement And Adjustment

    12. Retest for leaks. If bubbles form, SHUT DOWN GAS AND Remove regulator cover screw from the outlet pressure REPAIR LEAKS IMMEDIATELY. regulator and turn screw clockwise to increase pressure or counterclockwise to decrease pressure. Replace 13. Turn ON electrical power and gas supply to the system. regulator cover screw.
  • Page 18 Temperature Rise Check Limit Check Check the temperature rise through the unit by placing Check limit control operation after 15 minutes of operation thermometers in supply and return air registers as close to by blocking the return air grille(s). the unit as possible. Thermometers must not be able to 1.
  • Page 19: Cooling Startup

    OOLING TARTUP Design superheat & subcooling @ 95 °F NOTE: Check all manual reset limit controls in heating circuit if outdoor ambient temperature cooling mode does not operate. Models # Superheat ± 2°F Subcooling ± 3°F Compressor Protection Devices *PG1424***M The compressor includes components which are designed *PG1430***M to protect the compressor against abnormal operating...
  • Page 20 cycle is completed, and ignition is reattempted. The control Open Thermal Protection Device will repeat this routine three times if a measurable combustion If the primary limit switch opens, the gas valve is immediately is not established. The control will then shut off the induced de-energized, the induced draft and air circulating blowers draft blower and go into a lockout state.
  • Page 21: Abnormal Operation - Cooling

    BNORMAL PERATION OOLING ABINET INISH AINTENANCE Use a fine grade automotive wax on the cabinet finish to Short Cycle Compressor Delay maintain the finish’s original high luster. This is especially The automatic ignition control has a built-in feature that important in installations with extended periods of direct prevents damage to the compressor in short cycling sunlight.
  • Page 22: Main Burner Flame (Qualified Servicer Only )

    6. To reduce the chances of repeated fouling of the heat 5. Replace burners and manifold, inspect the burner exchanger, perform the steps listed in “Startup, assembly for proper seating of burners in retention slots. Adjustments, and Checks”. 6. Reconnect electrical power and gas supply. URNER LAME UALIFIED...
  • Page 23 BLOWER PERFORMANCE DATA - SINGLE PHASE *PG1424040M41** - Rise Range: 25° - 55° T4 COOLING T5 COOLING T1 HEATING SPEED T2 HEATING SPEED T3 HEATING SPEED E.S.P. SPEED SPEED WATTS RISE WATTS RISE WATTS RISE WATTS WATTS 1,050 1,095 1,010 1,060 1,025 *PG1424060M41** - Rise Range: 30°...
  • Page 24 BLOWER PERFORMANCE DATA - SINGLE PHASE *PG1436040M41** - Rise Range: 25° - 55° T4 COOLING T5 COOLING T1 HEATING SPEED T2 HEATING SPEED T3 HEATING SPEED E.S.P. SPEED SPEED WATTS RISE WATTS RISE WATTS RISE WATTS WATTS 1,115 1,265 1,305 1,440 1,075 1,230...
  • Page 25 BLOWER PERFORMANCE DATA - SINGLE PHASE *PG1448060M41** - Rise Range: 30° - 60° T4 COOLING T5 COOLING T1 HEATING SPEED T2 HEATING SPEED T3 HEATING SPEED E.S.P. SPEED SPEED WATTS RISE WATTS RISE WATTS RISE WATTS WATTS 1,055 1,380 1,415 1,570 1,780 1,000...
  • Page 26 BLOWER PERFORMANCE DATA - SINGLE PHASE *PG1461080M41** - Rise Range: 30° - 60° T1 LOW STAGE HEATING T2 HIGH STAGE HEATING T3 LOW STAGE T4 HIGH STAGE T5 COOLING SPEED SPEED HEATING SPEED COOLING SPEED SPEED E.S.P. WATTS RISE WATTS RISE WATTS WATTS...
  • Page 27 IGNITION CONTROL DIAGNOSTIC INDICATOR CHART (SINGLE STAGE MODELS ONLY) Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual Internal Control Failure 1 Flash External Lockout 2 Flashes Pressure Switch Stuck Open 3 Flashes Pressure Switch Stuck Closed 4 Flashes Thermal Protection Device Open 5 Flashes...
  • Page 28 IGNITION CONTROL DIAGNOSTIC INDICATOR CHART (TWO-STAGE MODELS ONLY) Red Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual Internal Control Failure 1 Flash External Lockout 2 Flashes Pressure Switch Stuck Open 3 Flashes Pressure Switch Stuck Closed 4 Flashes Thermal Protection Device Open 5 Flashes...
  • Page 29: Appendix

    APPENDIX UNIT DIMENSIONS FLUE EXHAUST HOOD FLUE EXHAUST HEAT EXCHANGE ACCESS PANEL POWER WIRE ENTRANCE CONTROL WIRE ENTRANCE EXHAUST FLUE HOOD BLOWER ACCESS PANEL...
  • Page 30: Wiring Diagrams

    *PG14(24, 30, 36, 42)***M41* * WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 31 *PG14(24, 30, 36, 42)***M41* * WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 32 PG1448***M41* * WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. COMP CH OPTIONAL CONNECTED AT L1, L2 CH OPTIONAL NOTE 3 SEE NOTE 3...
  • Page 33 *PG1448***M41* * WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. COMPONENT LEGEND SUPPLY VOLTAGE A UXILLARY LIMIT SW ITCH 208-230/1/60 COMP COMPRESSOR...
  • Page 34 *PG1461***M41** WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. SEE NOTE 6 SEE NOTE 3 COMP POWER SUPPLY BL BK 208-230/1/60 SEE NOTE 3...
  • Page 35 *PG1461***M41** WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. FACTOR Y WIRING COM PONENT LEGEND AUXILLARY LIMIT SWITCH LINE VOLTAGE TRANSFORMER HIGH SUPPLY VOLTAGE...
  • Page 36: Minimum Clearances

    MINIMUM CLEARANCES Clearance in accordance with local installation codes, the requirements of the gas supplier and the manufacturer’s installation instructions. Dégaugement conforme aux codes d’installation locaux, aux exigences du fournisseur de gaz et aux instructions d’installation du fabricant. 48" MIN 12"...
  • Page 37 PACKAGE UNITS - DUAL FUEL & GAS HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS We strongly recommend a bi-annual maintenance checkup be performed by a qualified service agency before the heating and cooling seasons begin. NNUAL NSPECTION UALIFIED ERVICER Your package unit should be inspected by a qualified installer, or service agency at least twice every year.
  • Page 38: Start0Up Checklist

    Start-up Checklist *Store in job file Air Conditioning & Heating Date: ___________________________________ Location: __________________________________________ Model Number: ___________________________________ __________________________________________ Serial Number: ___________________________________ __________________________________________ Technician: ___________________________________ Unit #: __________________________________________ Pre Start-Up (Check each item as completed) Verify all packaging material has been removed. Remove all shipping brackets per installation instructions.
  • Page 39 Start-up Checklist Air Conditioning & Heating Start-Up (Insert the values as each item is completed.) ELECTRICAL Supply Voltage L1 - L2 L2 - L3 L3 - L1 Circuit 1 Compressor Amps Circuit 2 Compressor Amps Blower Amps Condenser Fan Amps Fan 1 Fan 2 Fan 3...
  • Page 40 Goodman Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com - or - www.amana-hac.com 2014-2019 Goodman Company, L.P. © is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX, USA. All rights reserved.