Step 6 - Make Outdoor-Air Adjustments And Install Outdoor-Air Hood - Payne PA1R Series Installation, Start-Up And Service Instructions Manual

Single package rooftop electric heating / electric cooling units
Table of Contents

Advertisement

LEGEND
AHA — Adjustable Heat Anticipator
CC
— Cooling Compensator
TC
— Thermostat-Cooling
TH
— Thermostat-Heating
Field Wiring
Factory Wiring
NOTES:
1. Connect Y2 when unit is equipped with an economizer.
2. Connect W1 when unit is equipped with an accessory 1-module heater
package. Connect W1 and W2 when unit is equipped with an acces-
sory 2-module heater package.
Fig. 10 — Low-Voltage Connections
CONDENSER
FAN
RACEWAY
(HIDDEN)
Fig. 11 — Low-Voltage Location
R
Y1
Y2
W1
W2
G
C
X
LOW-VOLTAGE WIRING
CONNECTION
VI. STEP 6 — MAKE OUTDOOR-AIR ADJUSTMENTS AND
INSTALL OUTDOOR-AIR HOOD
A. Manual Outdoor-Air Damper
Assembly:
1. Determine quantity of ventilation required for building.
Record amount for use in Step 8.
2. Remove and save outdoor-air opening panel and screws.
See Fig. 12.
3. Separate hood and screen from basepan by removing the
4 screws securing them. Save all screws.
4. Replace outdoor-air opening panel.
5. Place hood on front of outdoor-air opening panel. See
Fig. 13 for hood details. Secure top of hood with the
4 screws removed in Step 3. See Fig. 14.
OUTDOOR
AIR OPENING
PANEL
Fig. 12 — Damper Panel With Manual Outdoor-Air
Fig. 13 — Outdoor-Air Hood Details