II PAIZ 24-1 Cancels: 11/15/97 CONTENTS Page SAFETY CONSIDERATIONS ...... I. General ........RECEIVING INSTALLATION ....5-10 I. Step 1 -- Check Equipment ....Step 2 -- Provide Unit Support ....Ill. Step 3 -- Provide Clearances ....IV. Step 4 -- Place Unit ......
Page 2
REQUIRED CLEARANCES TO COMBUSTIBLE MAT'L -- mm (in.) _294 _4080 [11.51] [16.N6] Top of Unit ........Duct Side of Unit ........Side Opposite Ducts ........ Bottom of Unit ........NEC REQUIRED CLEARANCES -- mm (in.) Between Units, Power Entry Side ..... 1066.8 (42.00) Unit and Ungrounded Surfaces,...
Page 3
REQUIRED CLEARANCES TO COMBUSTIBLE MAT'L -- mm (in.) _2940 _4080 [II,5?] [15,06] Top of Unit ........Duct Side of Unit ........£ Side Opposite Ducts ........ Bottom of Unit ........NEC REQUIRED CLEARANCES -- mm (in.) Between Units, Power Entry Side ..... 1066.8 (42.00) Unit and Ungrounded Surfaces,...
Page 4
REQUIRED CLEARANCES TO COMBUSTIBLE MAT'L -- mm (in.) _352,r [BSR] Top of Unit ........117.B _35Z8 _537 Duct Side of Unit ........[4.B3] H3.Sfl [Lit3 Side Opposite Ducts ........ Bottom of Unit ........NEC REQUIRED CLEARANCES -- mm (in.) Between Units, Power Entry Side ..... 1066.8 (42.00) Unit and Ungrounded Surfaces, Power...
RECEIVING AND INSTALLATION III. STEP 3 -- PROVIDE CLEARANCES required minimum service clearances clearances I. STEP I--CHECK EQUIPMENT combustibles shown in Fig. 2-4. Adequate ventilation A. Identify Unit condenser must be provided. The unit model number and serial number are stamped condenser pulls through...
V. STEP 5 -- SELECT AND INSTALL DUCTWORK When designing installing ductwork, consider following: The design installation of the duct system must be in accordance with: • the standards of the NFPA (National Fire Protection Association) for installation of nonresidence type air con ditioning and ventilating...
• Insulate and weatherproof all external ductwork. Insulate Condensate water be drained directly onto roof and cover with a vapor barrier all ductwork passing through rooftop installations (where permitted) or onto a gravel apron conditioned spaces. Follow latest Sheet Metal and Air Con ground level installations.
Page 8
Route thermostat wiresthrough grmnmet providing a drip loopatthepanel. C onnect lowvoltage leads tothethermo statasshown in Fig.13. Theunittransformer supplies 2 4-vpower f orcomplete s ys- temincluding accessory electrical heater. T ransformer is facto W wiredfor230v operation. If supply voltage is 208 v, rewire transformer primary asdescribed in theSpecial Pro cedures for208-v O peration s ection b elow.
Page 9
Table 3 -- Electrical Data DISCONNECT NOMINAL VOLTAGE COMPRESSOR ELECTRIC HEAT POWER SUPPLY SIZE UNIT VOLTAGE RANGE PA1Z (V-Ph-Hz) Nominal kW* MOCP --/-- --/-- 16.9/ !6.9 20/ 20 16/ !6 208/230-1-60 10.9 61.0 3.8/ 5.0 18.1/20.8 25.6/ 29.0 30/ 30 24/ 27 7.5/10.0 36.1/41.7...
PRE-START-UP START-UP Use the Start-Up Checklist supplied at the end of this book, and proceed as follows: I. CHECK FOR REFRIGERANT LEAKS Locate repair refrigerant leaks and charge tile unit follows: 1. Using both high and low pressure ports, locate leaks reclaim remaining...
Page 12
B. Low Charge Cooling Cooling Charging Charts, Fig. 15 20. Vary refrigerant until conditions of the appropriate chart met. Note that charging charts are different fl'om the type normally used. Charts based on charging units to the correct super- heat for the various operating...
Page 13
IIlIll[Irillilllllji 110- IIlllll Ili_ II]lll' IIIIIII IIIIIIi IIIIIlIII]illllllll! !lllllljI' IIIl]ll]j IIILI IIIII]1]1 111111111 IIIIlII]l 111111111 Illlltl]I 111111111 Illl_ll 68_ lo I]1111[ 111111111 IIIIIII]] IIlllll IIIIIII_ jljllJ I I I I I II I I I I I_ o_621 LA"7 _ i J,,_f J...r i i .b,.P'7 I I L_...
Airflow can be changed by changing the lead connections the blower motor, energized. NOTE: PA1Z030 and 060 units are equipped with a time- Units PA1Z024,036,048, and 060 blower motors are factory delay relay.
Page 15
Table 4 -- Dry Coil Air Delivery* -- Horizontal Discharge (Deduct 10% for 208 Volt Operation) 230 AND 460 VOLT HORIZONTAL DISCHARGE UNIT MOTOR External Static Pressure (in. wg) PA1Z SPEED DELIVERY Watts Watts 1131 !090 1038 Watts High 1391 !338 1285 !200...
Table 7 -- Accessory Electric Heat Pressure Drop Only qualified service personnel should perform mainte- nance and service procedures that require unit top removal. (in. wg) Refer" to the following top removal procedures: HEATER 1. Remove 7 screws on unit top cover surface.
splash w ateronmotors, insulation, wiring, o rairfilter(s). Fox" Remove top panel to locate all the electrical controls best r esults, spray condenser coilfinsfrominside tooutside wiring. Check all electrical connections for tightness. Tighten theunit.Onunitswithanouter a ndinner condenser coil, b e suretoclean between thecoils. B esuretoflushall dirt and all screw connections.
Page 18
TROUBLESHOOTING COOLING CHART SYMPTOM CAUSE REMEDY Compressor and con- Power failure Call power company. denser fan will not Fuse btown or circuit breaker tripped Replace fuse or reset circuit breaker. start. Defective thermostat, contactor, transformer, Replace component. or control retay Insufficient line voltage Determine cause and correct.
Page 20
START-UP CHECKLIST (Remove and Store in Job File) I. PRELIMINARY INFORMATION SERIAL NO.: MODEL NO.: TECHNICIAN: DATE: II. PRE-START-UP checkmark in box as each item is (insert completed) [] VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT [] VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS [] CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS...
Need help?
Do you have a question about the PA1Z030 and is the answer not in the manual?
Questions and answers