Pavilion PV199DV Installation Manual page 62

Condensing gas combi boiler
Hide thumbs Also See for PV199DV:
Table of Contents

Advertisement

[I:07_bSt (Boost Timing)]
This setting is to increase the set temperature
during unit cold start up if the actual room
temperature doesn't reach the thermostat set
temperature quick enough, the Boost time
function will increase the set temperature of the
Combi Boiler by 10°F (5°C) after the selected Boost
time setting has passed.
Example:
Room thermostat set at 72°F, Combi Boiler set
temp at 140°F, and Boost time function set
to 30 min.
If the room temperature does not reach 72°F
within 30 min then the Combi Boiler will
increase its set temp from 140°F to 150°F.
settings:
OFF (Boost Timing is deactivated.),
1 - 120 min (Time before starting the boost
operation.)
NOTE When [I:01_HCt] setting is "2:or" or
"3:EC", this function will appear.
[I:08_Air (Air Handler)] (page 51)
This function needs to be turned "on" if an Air
Handler is being used as a heating type.
The Air Handler function is designed to stop the
Air Handler's pump and fan operation when the
Combi Boiler's operation is not suitable for the Air
Handler.
settings:
OFF (When an air handler is not used.),
ON (When an air handler is used.)
[I:09_EPP (External Pump)] (page 51)
This setting can activate or deactivate the
terminals in the Combi Boiler for an External Pump
(secondary pump) on the circuit board.
settings:
OFF (When an external pump is not used.),
ON (When an external pump is used.)
62
Installer Mode (Parameter Settings)
1 sec.
(Default setting =
1 sec.
(Default setting =
1 sec.
(Default setting =
[I:10_rFt (Re Fire Time)]
This function is to set up the interval time in
Heating Mode to prevent inconsistent heating.
If the selected time passes and the Combi Boiler's
inside temperature drops, this function will
automatically reignite the burner in the Combi
Boiler.
settings: 0 - 20 min
[I:11_Pot (Pump Overrun Time)]
This mode is to control how long the pump will run
after the heating demand is satisfied.
This setting is to prevent unnecessary running of
the pump and extend the life of the pump.
OFF
)
settings: OFF, 1 - 40 min
[I:12_bFt (Differential Burner OFF Temperature)]
settings: 0 - 27°F (0 - 15°C)
[I:13_bot (Differential Burner ON Temperature)]
settings: 5 - 27°F (3 - 15°C)
When the internal temperature of the Combi Boiler
OFF
)
is too high or low the unit will stop burning or start
burning.
Burner OFF Temperature
= Heating Set Temperature + [I:12_bFt]
Burner ON Temperature
= Heating Set Temperature - [I:13_bot]
OFF
)
1 sec.
(Default setting =
1 sec.
(Default setting =
1 sec.
13°F (7°C)
(Default setting =
1 sec.
18°F (10°C)
(Default setting =
0 min
)
OFF
)
)
)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ghq-c3201wx-ff pb us

Table of Contents