Parameter Settings
[I:00_FC (Fahrenheit/Celsius)]
This mode is for changing temperature and flow
rate units on the Operation Display.
To change the setting: Press and hold the
button for approximately 5 seconds.
button, °C→°F:
(°F→°C:
1: F
[
]
2: C
[
]
NOTE This function will appear within
the first 10 minutes of connecting
electrical power and before pressing
the ON/OFF button.
[I:01_HCt (Heating Control Type)] (page 53,57)
This mode is for changing heating control type.
1: St
[
]
2: or
[
]
3: EC
[
]
60
Installer Mode (Parameter Settings)
1 sec.
button)
F: Fahrenheit & Gallon
All of the units shown on the
display screen are °F & GPM.
C: Celsius & Liter
All of the units shown on the
display screen are °C & LPM.
(Default setting =
1 sec.
St: Standard
You can change the Heating
Set Temperature by Operation
Display.
or: Outdoor Reset Control
Outdoor Reset Control is
activated.
EC: External Control (0-10 V)
External Control (0-10 V) is
activated.
(Default setting =
[I:02_tHS (Type of Heating System)] (page 53-56)
This mode is for choosing Type of Heating System,
when [I:01_HCt] setting is "2:or".
There are 6 typical Heating Systems that are
available.
For these 6 heating types the low and high
or
temperature points are pre-programmed.
(See ranges to the below)
If "2:AH" is selected, additional steps are needed
to be programmed, see [I:08_Air].
To use custom low and high temperature points,
select "7:CU" and follow [I:03_Hot], [I:04_Lot],
[I:05_HHt] and [I:06_HLt] to set custom low and
high temperature points.
1:Ft
1: F
)
2:AH
3:CI
4:Lr
5:rF
6:rA
7:CU
1: Ft
[
2: AH
[
3: CI
[
4: Lr
[
5: rF
[
1: St
)
6: rA
[
7: CU
[
NOTE When [I:01_HCt] setting is "1:St" or
1 sec.
LOW [°F (°C)]
120 (49)
140 (60)
100 (38)
80 (27)
80 (27)
120 (49)
[Min Set-point +30 (17)]
80 (27) or more
[Max Set-point - 30 (17)]
Ft: Fin Tube Baseboard
]
AH: Air Handler
]
CI: Cast Iron Baseboard
]
Lr: Low Mass Radiant Floor
]
rF: Mass Radiant Floor
]
rA: Radiator
]
CU: Custom
]
(Default setting =
"3:EC", this function will not appear.
HIGH [°F (°C)]
180 (82)
180 (82)
170 (76)
140 (60)
120 (49)
170 (76)
or more 180 (82)