CAUTION
Installation in the vicinity of gas ranges,
stoves, fans, and range hoods
• Avoid installation above gas ranges or stoves.
• Avoid installation between the kitchen fan
and stove. If oily fumes or a large amount of
steam are present in the installation location,
take measures to prevent the fumes and
steam from entering in the appliance.
NOT
CORRECT
• Install in a location where the exhaust gas
flow will not be affected by fans or range
hoods.
CORRECT
14
Choosing an Installation Location
NOT
CORRECT
NOTICE
• Place the appliance for easy access for
maintenance and repair.
• Do not install the Combi Boiler in a location
where the appliance will be exposed to
excessive winds.
• Locate the appliance in an area where
leakage from the appliance or connections
will not result in damage to the area adjacent
to the appliance or to the lower floors of the
structure. When such installation locations
cannot be avoided, a suitable drain pan,
adequately drained, must be installed under
the appliance. The pan must not restrict
combustion air flow.
• As with any water heating appliance, the
potential for leakage at some time in the life
of the product does exist. The manufacturer
will not be responsible for any water damage
that may occur.
• Water quality:
If this Combi Boiler will be installed in a
location where the hardness of the supply
water is high, scale Build-up may cause
damage to the Plate Heat Exchanger.
Perform suggested treatment and
maintenance measures in reference to "8.2
Water Treatment".
Damage to the Combi Boiler as a result of the
below is not covered by the Pavilion Limited
Warranty.
- Water in excess of 12 gpg (200 mg/L) of
hardness
- Poor water quality (see the following table)
Contaminant
Total Hardness*
Aluminum
Chloride
Copper
Iron
Manganese
pH
Total Dissolved Solids 500 mg/L or less
Zinc
Sulfate
Residual chlorine*
Source: EPA National Secondary Drinking Water
Regulations (40 CFR Part 143.3)
* Maximum limit suggested/approved by the
manufacturer.
NOTE Consult with the customer concerning
the location of installation.
Maximum Allowable Level
200 mg/L (12 gpg) or less
0.05 to 0.2 mg/L or less
250 mg/L or less
1.0 mg/L or less
0.3 mg/L or less
0.05 mg/L or less
6.5-8.5
5 mg/L or less
250 mg/L or less
4 mg/L or less