 Use a dedicated tool to peel the coating to avoid damage to the
 Be careful if the shielded wires do not extend the sheath end
 Atmospheric pressure is introduced into an instrument via the
 Always attach a crimp terminal that fits with the core wire.
3) Open the terminal box lid and insert the cable from the terminal opening deep into the gasket (See
Figure 8-3 below).
4) Tighten the gland and seal the terminal opening. (See Figure 8-3 below).
Terminal opening
 Pass the cable through the gasket and tighten it with the gland
CAUTION
cable core.
face.
cable. If the cable is pressed due to a clamp, bush, or extreme
bend in the middle of the cable, or if the cable is long, the
exhaustion of pressure takes time. In this case, an output error
may be caused because of pressure within the case or a change
in temperature. Conduct wiring not to seal the cable end with
tape or adhesive. Avoid using the cable with poor ventilation
performance (no clearance within the cable).
Terminal box lid
Washer
Gland
Cable
Gasket
Terminal box
< Figure 8-3 >
to prevent the intrusion of water.
CAUTION
15
Terminal block
Y-KH15-007A Rev.3