User Manual for
KJ16 Intrinsically Safe
Pressure Transmitter
7.5

Advertisement

Table of Contents
loading

Summary of Contents for Nagano Keiki KJ16

  • Page 1 User Manual for KJ16 Intrinsically Safe Pressure Transmitter...
  • Page 2: For Proper And Safe Use

    For Proper and Safe Use Thank you for purchasing the KJ16 Intrinsically Safe Pressure Transmitter. To use this product safely and properly, read this user manual carefully. This product is used to measure pressure in a wide range of industrial processes. Incorrect use of it causes failures, which may result in damage including faults or accidents.
  • Page 3: Precautions For Handling Product

    Otherwise, the product fails or is damaged, which causes injury or damage to the surrounding environment. * These precautions are selected from our common safety precautions for all products that correspond to this product. KJ16-specific precautions are further described in detail in the following sections. TY-KJ16-001A Rev.2...
  • Page 4: Table Of Contents

    4. Specifications ................8 ■ 4.1 Product specifications ................... 8 ■ 4.2 Intrinsically safe specifications ................9 5. Dimensions ................11 ■ 5.1 Standard model ....................11 ■ 5.2 Threads ....................... 12 ■ 5.3 Diaphragm at the edge ..................13 TY-KJ16-001A Rev.2...
  • Page 5 12. Maintenance ................. 33 ■ 12.1 Periodic inspection ................... 33 ■ 12.2 Service ......................33 13. Product Warranty & Export Administration Regulations .... 34 ■ 13.1 Product warranty ....................34 ■ 13.2 Export Administration Regulations ..............34 13. Others ................... 34 TY-KJ16-001A Rev.2...
  • Page 6: Preface

    A detection circuit has a full-bridge system where all of four edges of a bridge consist of semiconductor strain gauges. Electric signals in proportion to distortion can be obtained from this bridge circuit. Electric signals TY-KJ16-001A Rev.2...
  • Page 7: Model Number Structure

    *1 Wetted material used for this type: F: 9/16-18UNF (equivalent to Autoclave “4: Diaphragm (SUS630 (17-4PH)), Engineers F250C) Fitting (SUS316)” only V: G3/8A (Diaphragm on the edge type * 1 to 10MPa are available) < Fig. 3-1 Model Number Structure > TY-KJ16-001A Rev.2...
  • Page 8: Specifications

    Pressure range 0 to 0.5, 1, 2, 3.5, 5, 10, 20, 35, 50, 70, 100 MPa 0 to 1, 2, 3.5, 5, 10 MPa (up to 35 MPa for KJ16-□□G) 200% of pressure range SUS630 (except 35 & 50 MPa (150%) and...
  • Page 9: Intrinsically Safe Specifications

    4.2.2 Insulating barrier (Non-hazardous area) Specifications of a recommended insulating barrier (safety barrier) paired with the KJ16 pressure transmitter are shown in the table below. An insulating barrier does not need to be grounded as defined in the intrinsically safe standards as it is isolated from the intrinsically safe circuit.
  • Page 10 * Choice of safety barriers available. <Table 4-3> 4.2.3 Zener barrier (Non-hazardous area) The specifications of a recommended Zener barrier (safety barrier) paired with the intrinsically safe KJ16 pressure transmitter are shown in the table below: Manufacturer Cooper Industries Japan K.K. Model MTL7787+ Type approval No.
  • Page 11: Dimensions

    ■ 5.1 Standard model Terminal layout Power (+) Ground Power (-) φ6.2 Shielded cable < Fig. 5-1 KJ16-9□□ (Terminal box (large)) > A (red): power (+) C (white): power (-) E (shield): earth *1 Screws on the side are for fixing the case.
  • Page 12: Threads

    Power (-) HEX. *1 Screws on the side are for fixing the case. Do not use them for earth connection. < Fig. 5-3 KJ16-7□□ (Terminal box (small)) > ■ 5.2 Threads KJ16-□6□ KJ16-□7□ KJ16-□8□ KJ16-□9□ KJ16-□2□ KJ16-□3□ KJ16-□4□ (G1/4B) (G3/8B)
  • Page 13: Diaphragm At The Edge

    Ground Power (+) Power (-) φ6.2 Shielded cable HEX. O ring (P14) < Fig. 5-7 KJ16-9V4 (Terminal box (large)) A (red): power (+) C (white): power (-) E (shield): earth HEX. O ring (P14) < Fig. 5-8 KJ16-6V4 (Connector type) >...
  • Page 14: Edge Dimensions

    *1 Screws on the side are for fixing the case. Do not use them for earth connection. < Fig. 5-9 KJ16-7V4 Terminal box (small) > ■ 5.4 Edge Dimensions < Fig. 5-10 (1 to 2 MPa pressure range) > < Fig. 5-11 (3.5 to 10 MPa pressure range) >...
  • Page 15: Diaphragm On The Edge Type/ Connection Part Dimensions Used By User

    (1) Do not apply vibration as much as possible in transporting the product, as is the case with other electric meters. (2) Never hit or drop the product. ! CAUTION Do not drop this product or give a shock to it. ● Otherwise, the product may become completely inoperable. TY-KJ16-001A Rev.2...
  • Page 16: Precautions For Unpacking

    Do not put a piece of wire into a pressure inlet. ● The diaphragm is damaged, which causes incorrect behavior. Terminal box type should be oriented such that gland points ● upward to prevent water from entering through the cable. TY-KJ16-001A Rev.2...
  • Page 17: Safety Barrier

    Provide an earth ground through the piping, since it is required ● to obtain an earth ground from the KJ16 main unit (fitting part). In the case where an earth ground at the pipe is unavailable, use the earth terminal of this product (connector: shielded wire of the cable;...
  • Page 18: Precautions For Possible Water Sprinkling On Transmitter (Terminal Box Type)

    φ 6.3 is sprinkled in every direction (from a distance of 2.5 m to 3 m) to a surface area of 1 m2 for 1 minute, 3 minutes or longer in total, to make sure that no water leaks in (no harm). TY-KJ16-001A Rev.2...
  • Page 19: Wiring And Connection

    φ7 φ6 to 7 KJ16-7 (standard) Terminal G3/8 φ8 φ7 to 8 box (small) φ9 φ8 to 9 0.25 to 1.65 KJ16-9 φ10 φ9 to 10 Terminal G1/2 (standard) box (large) φ11 φ10 to 11 <Table 8-1> TY-KJ16-001A Rev.2...
  • Page 20 *1 If insulating barrier is used, provide an earth ground through the piping, since it is required to obtain an earth ground from the KJ16 main unit (fitting part). In the unlikely event that earth grounding from the piping is impossible, use the shielded wire to make an earth ground. However, if both the KJ16 main unit and the shielded wire are grounded, make a 1-point grounding so as not to generate a potential difference.
  • Page 21 ● the gland to prevent the intrusion of water. Connect the wire to the terminal block. The recommended tightening torque for KJ16-7□□ terminal block: 1.2 N・m. The recommended tightening torque for KJ16-9□□ terminal block: 1.2 N・m. CAUTION To use a bare crimp terminal, use an insulation tube to keep ●...
  • Page 22: M12 Connector Transmission Cable

    (mm cables/ mm) Shielded cable −20 to 60°C Φ 6.2 7/ 0.18 (standard) (AWG25) −20 to 105°C Φ 6.0 Heat‐resistant cable 12/ 0.18 (AWG23) −40 to 80°C Φ 6.0 Cold‐resistant cable 12/ 0.18 (AWG23) < Table 8-2 > TY-KJ16-001A Rev.2...
  • Page 23: System Configuration Diagram

    < Fig. 8-5 > Earth ground needs to be obtained from the fitting part of the KJ16 main unit through the piping. In the unlikely event that earth grounding from the piping is impossible, ground the earth using this product's earth terminal (connector: cable shielded wire / terminal box: terminal board No.
  • Page 24: Wiring Example

    8.4.1 Insulating barrier Install the intrinsically safe equipment (KJ16) in a hazardous area and the safety barrier (insulating barrier) and general equipment (power supply, receiving device) in a non-hazardous area as shown in the wiring diagram in the following pages. If you purchase an insulating barrier, Class A grounding required for intrinsically safe device is not necessary.
  • Page 25 < Table 8-3 > Earth ground needs to be obtained from the fitting part of the KJ16 main unit through the piping. In the unlikely event that earth grounding from the piping is impossible, ground the earth using this product's earth terminal (connector: cable shielded wire / terminal box: terminal board No.
  • Page 26 < Table 8-4 > Earth ground needs to be obtained from the fitting part of the KJ16 main unit through the piping. In the unlikely event that earth grounding from the piping is impossible, ground the earth using this product's earth terminal (connector: cable shielded wire / terminal box: terminal board No.
  • Page 27 < Table 8-5 > Earth ground needs to be obtained from the fitting part of the KJ16 main unit through the piping. In the unlikely event that earth grounding from the piping is impossible, ground the earth using this product's earth terminal (connector: cable shielded wire / terminal box: terminal board No.
  • Page 28 < Table 8-6 > Earth ground needs to be obtained from the fitting part of the KJ16 main unit through the piping. In the unlikely event that earth grounding from the piping is impossible, ground the earth using this product's earth terminal (connector: cable shielded wire / terminal box: terminal board No.
  • Page 29 8.4.2 Zener barrier Install the intrinsically safe equipment (KJ16) in a hazardous area and the safety barrier (insulating barrier) and general equipment (power supply, receiving device) in a non-hazardous area as shown in the wiring diagram below. Additional DIN rail with a width of 35 mm is required for the installation of a safety barrier.
  • Page 30: Intrinsically Safe Device And Safety Barrier

    ! CAUTION Follow the guidance of “USERS’ GUIDELINES for Installations for ● Explosive Atmospheres in General Industry (Protection from gas explosion 1994)” issued by the Technology Institution of Industrial Safety for the installation of intrinsically safe devices. TY-KJ16-001A Rev.2...
  • Page 31: Operation (Energization)

    • Change the direction of the product toward the source to change an incidence angle to a board. • Install an electromagnetic shield in the source or the product. • Ground the product so that the specified ground point is electrically grounded (See "5.1 and 5.3"). TY-KJ16-001A Rev.2...
  • Page 32: Storage

    • Places exposed to inclination, vibration or shock (including during transportation) • Places where chemicals are stored or gases are generated. • Places exposed to direct sunlight, or inside a car at high temperature TY-KJ16-001A Rev.2...
  • Page 33: Maintenance

    If a failure is suspected, check any cable breakage or the power supply voltage before contacting the agency where you purchased the product or our sales office nearest you. Pack the product so that it is not damaged during transportation, with a note describing the failure attached to the package. TY-KJ16-001A Rev.2...
  • Page 34: Product Warranty & Export Administration Regulations

    This user manual does not cover details or all variants of equipment. It is not intended to support all events involved that you encounter in installing and maintaining the product. Therefore, when you need further detailed information, or when the manual does not provide enough information suited for your intent, contact us. TY-KJ16-001A Rev.2...
  • Page 35 This is an English translation of the Japanese original (TY-KJ16-001 Rev.2). All information and specifications in this user manual are subject to change without notice. We have the copyright on all the information described in this user manual. Copying or reprinting without permission is prohibited.