Appendix B
Torque Table (continued)
KTV Models
Table B.4 lists the torque for terminal block connection. (For TB locations, see Figure B.d.)
Table B.4
Input TB
Battery TB
OUTPUT TB
Ground
Input TB
Battery TB
OUTPUT TB
Ground
SU60KTV
Torque lb-in (kgf-cm)
50 (57.6)
50 (57.6)
50 (57.6)
217 (250)
SU80KTV
50 (57.6)
50 (57.6)
50 (57.6)
217 (250)
Fig B.d.
127
Screwdriver
Slotted Screwdriver
Slotted Screwdriver
Slotted Screwdriver
17mm Socket Wrench
5mm Hex Wrench
5mm Hex Wrench
5mm Hex Wrench
17mm Socket Wrench