Fuse And Wiring Selection - VENCO VHR Series Installation, Operation, & Maintenance Instruction

Heat pump heat recovery units
Table of Contents

Advertisement

Fuse and wiring selection

16.
MODEL
VHR 05 DX
VHR 07 DX
VHR 10 DX
VHR 15 DX
VHR 20 DX
VHR 21 DX
VHR 30 DX
VHR 40 DX
MODEL
VHR 05 DX
VHR 07 DX
VHR 10 DX
VHR 15 DX
VHR 20 DX
VHR 21 DX
VHR 30 DX
VHR 40 DX
2016.09
ELECTRIC POWER
1290W
1350W
2020W
3270W
3820W
3820W
5986W
8400W
1,5
2,5
26
43
25
41
17
28
17
67
112
80
Fuse
VOLTAGE - HZ
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
400 volt – 50 Hz
400 volt – 50 Hz
Wiring
Cable section [mm²]
4
6
Cable length [m]
69
103
66
99
44
66
27
41
23
35
23
35
180
249
128
192
FUSES
10A
10A
16A
20A
25A
25A
3X16A
3X16A
10
16
110
68
109
58
93
58
93
320
28 / 28