Appendix-5 Electrical Cable And Fuse Selection Tables - VENCO VHR Series Installation, Operation, & Maintenance Instruction

Table of Contents

Advertisement

17.8.

APPENDIX-5 Electrical Cable And Fuse Selection Tables

Table 17.8.1. Heat Recovery Unit Electrical Power Supply and Circuit Breaker Selection Table
MODEL
VHR 04
VHR 07
VHR 09
VHR 11
VHR 16
VHR 20
VHR 23
VHR 29
VHR 36
VHR 51
MODEL
VHR 04 EC
VHR 09 EC
VHR 11 EC
VHR 16 EC
VHR 29 EC
VHR 36 EC
VHR 51 EC
*The circuit breaker must cut L/N at the same time.
2019.10
POWER
ELECTRICAL CONNECTION
CONSUMPTION
104 Watt
204 Watt
310 Watt
420 Watt
450 Watt
1030 Watt
1030 Watt
1100 Watt
1100 Watt
1100 Watt
POWER
ELECTRICAL CONNECTION
CONSUMPTION
110 Watt
340 Watt
340 Watt
1050 Watt
1220 Watt
1560 Watt
2600 Watt
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
230 volt – 50 Hz
CIRCUIT BREAKER*
2 Ampere
2 Ampere
2 Ampere
4 Ampere
4 Ampere
6 Ampere
6 Ampere
10 Ampere
10 Ampere
10 Ampere
CIRCUIT BREAKER*
6 Amper
6 Amper
6 Amper
10 Amper
10 Amper
10 Amper
16 Amper