Faults That Are Not Shown On The Display - Bosch ZBR16-3A Series Installation And Service Instructions Manual

Greenstar
Hide thumbs Also See for ZBR16-3A Series:
Table of Contents

Advertisement

17.3 Faults that are not shown on the display

Appliance faults
Combustion noise too loud; rumbling noises
Flow noises
Heating-up takes too long
Flue gas readings incorrect; CO levels too high
Violent ignition, poor ignition
DHW has unpleasant odor or has a dark color
Set supply temperature (e.g. of the FW200
control) exceeded
Condensate in air box
DHW temperature is not reached (combi boiler
ZWB..-3A only)
Heatronic is flashing (i.e. all buttons, all display
segments, burner indicator etc. are flashing)
Table 39 Faults not shown on the display
Greenstar
▶ Insert code plug correctly; replace if defective.
▶ Check gas type.
▶ Check inlet gas pressure; adjust if defective.
▶ Check flue gas system; clean or repair if defective.
▶ Check gas/air ratio in the combustion air and flue gas; replace gas valve if defective.
▶ Set pump speed correctly to match maximum output.
▶ Set pump mode.
▶ Set pump speed correctly to match maximum output.
▶ Set pump mode.
▶ Check gas type.
▶ Check inlet gas pressure; adjust if defective.
▶ Check flue gas system; clean or repair if defective.
▶ Check gas/air ratio in flue gas; replace gas valve if defective.
▶ Check gas type.
▶ Check inlet gas pressure; adjust if defective.
▶ Check power supply.
▶ Check electrodes for visual damage; replace if defective.
▶ Check flue gas system; clean or repair if defective.
▶ Check gas/air ratio; replace gas valve if defective.
▶ Check gas valve; replace if defective.
▶ Check burner; replace if required.
▶ Perform thermal disinfection of the DHW circuit.
▶ Replace sacrificial anode in the tank (if installed).
▶ Consult local water department.
▶ Switch off automatic anti-cycle timer, i.e., set value to 0.
▶ Set the required anti-cycle timer, e.g. default setting of 3 minutes.
▶ Insert diaphragm in the mixer unit per installation instructions; replace if defective.
▶ Insert code plug correctly; replace if defective.
▶ Check whether voltage (120 VAC) is present between terminal 1 and terminal 3; repair if
defective.
▶ Check turbine; replace if defective.
▶ Replace fuse Si 3 (24 V) (6.3 A fuse according to IEC default).
Elimination
6 720 806 992 (2015/03)
Faults | 79

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents