AI-7048 ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER
Operation Instruction
Ver. 7.5
Dimension D5

Advertisement

loading

Summary of Contents for Yudian AI-7048

  • Page 1 AI-7048 ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER Operation Instruction Ver. 7.5 Dimension D5...
  • Page 2 SUMMARY AI-7048 is capable of measuring and controlling four channels of temperature, and every channel can define its own input specification. AI-7048 can either work independently or cooperate with computer or PLC (Programmable Logic Controller). It features: ● Providing up to four channels of configurable inputs, and supporting multiple thermocouple inputs with auto reference junction compensation and linear voltage (mV) inputs with user defined scale.
  • Page 3 This is wiring graph for E5, and ALM is an optional alarm COMM module. 100-240VAC~ In AI-7048 size E5(DIN rail), E(48X96)mm, F(96X48)mm and A(96X96)mm, those size can have the alarm action COMM output after installed the following modules: L1 : Relay output module (2A/240VAC, NO+NC) L5 : Dual relay output module (2A/240VAC, NO), can change to NC by mode by change the parameter “...
  • Page 4 “OP1-OP4” LED: indicate the output of channel 1-4. DISPLAYS AND OPERATIONS ① Upper display window, displays PV, parameter code, etc. ① ② Lower display window, displays SV, parameter value, channel no. or alarm code. ③ Setup key, for accessing parameter table and ②...
  • Page 5 4. MODE indication light: When the instrument is communicating with the host computer, the light will keep flashing in random speed. When the instrument hasn’t received signal from the host computer more than 6 seconds, the indication light should flicker with the same light on time and light off time. It means: The on-off period is as long as 1.6 second means no communication and no alarm (it can be treated as normal);...
  • Page 6 When Cn=2, the lower window display the present value of channel 2 instead 1~ 4 input channels of the channel number. If several of AI-7048 has used, this parameter can define the AI-7048 to First display display assigned channel number on display. For example, when Cno=6, the channel setting controller will display channel number from 6~9.
  • Page 7 B=1; Change all of the low alarm to be low deviation alarm; when deviation value (PV – SV) < L.ALx, it will trigger the alarm. When (PV – SV) > L.ALx – HYSx, alarm off, set the L.ALx value to minimum will disable the alarm function.