Data Cable Termination

1.
Strip off outer jackets of cables being daisy chained.
Shielded cables only: Cut foil or braid flush to outer jacket.
DO NOT cut drain (shield) wire.
2.
Strip insulation from each of the conductors.
3.
Wind electrical tape (or use a cable tie) around the end of
the two cables to tie them together (see final drawing).
4.
Separate the blue and the blue-white wires from each other.
Then combine them with the matching wires from the other
cable; blue to blue and blue-white to blue-white.
5.
Twist remaining conductors ends with the matching colored
wires and fold ends in half. Isolate the unused pair with a
connector or tape.
6.
Reuse a wire insulation offcut (or heat shrink tubing) and fit
over drain wire.
7.
Terminate the wires on the pluggable screw terminal block.
(If used, shrink the heat-shrink tubing)
8.
Label or tag the cable appropriately.