6.3 ALARM TABLE

MESS. DISPLAY
DESCRIPTION
a01
no water alarm - temporary
a02
no water alarm - definitive
a03
Pressure transducer alarm.

6.4 ERROR TABLE

MESS. DISPLAY
DESCRIPTION
e00
no event.
Fault generico.
e01
(segnalazione memoria)
e02
temporary external error.
e03
Definitive external error.
e04
Communication error.
e05
over voltage error.
Under voltage error
e06
temporary.
Under voltage error
e07
definitive.
error due to the temporary absence of water. this occurs
when water is absent and the restart mechanism has been
activated. the will wait before restarting in order to attempt
to automatically reset the error.
this condition occurs when there is no water and the
automatic restart system has not activated or restart
attempts occurred already without managing to reset the
system functioning.
this alarm condition closes the J3 contact on the power
board for possible external signals (alarm light, siren, etc.)
this signal occurs when the control board cannot identify
the transducer pressure signal.
the error log appears when no errors have been signalled.
this error occurs in the presence of:
• internal module error
• overheating of the power module
• Pump failure
an external error occurs when there is a problem with the
power module. the module will not be operative during an
eXternaL error.
the definitive external error condition is indicated after the
temporary error condition is repeated 5 times.
this error condition occurs when the control board cannot
communication with the power part. this alarm condition
closes the J3 contact on the power board for possible
external signals (alarm light, siren, etc.).
this error occurs when the current absorbed by the module
is greater than triple the nominal current.
this condition can be caused when the pump is blocked
by foreign bodies.
this alarm condition closes the J3 contact on the power
board for possible external signals (alarm light, siren, etc.)
this error condition occurs when the voltage is 10% less
than the nominal voltage (230V).
this alarm condition closes the J3 contact on the power
board for possible external signals (alarm light, siren, etc.)
this error occurs when the temporary under voltage
condition is repeated 5 times.
ACTION
Check the water level in the first tank or the aqueduct pressure.
Wait for the programmed attempted restart or press the button
Start/StoP for a manual restart.
Check the water level in the first tank or the aqueduct pressure.
Press the button Start/StoP to manually restart the system.
Check the pressure transducer is correctly connected.
if the error occurs again, contact your nearest assistance centre.
ACTION
Press the Start/StoP button to attempt to exit this condition. in
case of a persistent error, contact technical support.
in this case, the module will attempt to restart normal functioning
after 5 minutes and will repeat this procedure up to five times.
Press the Start/StoP button to attempt to exit these conditions.
Please contact technical support of the error persists.
Press the Start/StoP button to attempt to exit this condition.
Please contact technical support of the error persists.
Cut the power off and wait until the Line Led switches off and
after which turn power back on. if the error condition occurs again,
contact your nearest assistance centre.
Cut off the power supply and wait for the Line Led to switch off.
Check the pump freely rotates and if necessary remove foreign
bodies that block correct functioning.
turn power back on.
if the error persists, contact your nearest assistance centre.
Press the button Start/StoP or cut the power off and wait until the
Line Led switches off and after which restart the system.
if the error occurs again, contact your nearest assistance centre.