Siemens RDB160BN Basic Documentation page 38

Room thermostat with bacnet ms/tp communication
Table of Contents

Advertisement

8
Communication
Control parameters
38 | 52
Name
P73
Supply air min. limitation for
cascade control and cooling
control
P74
Cascade factor between room
controller and supply air
controller
P75
Frost protection temperature
for supply air when supply air
temperature limitation is active
P76
Activate supply air temperature
limitation for
P77
Fan output type
P78
Valve 1 output type
P79
Valve 2 output type *)
*) Locked to On/Off when thermostat is set to 2-pipe with electric heater
application.
Factory setting
Range
12 °C
5...20 °C
3 °C
1...5 °C
8 °C
Heat valve open if
the supply air
temperature drops
below this
setpoint.
1 = Cooling
0 = Heating
control
control
1 = Cooling
control
2 = Both heating
and cooling
control
0 = 1- /2- / 3-
0 = 1- /2- /3-
speed fan
speed fan
1 = DC fan
0 = DC valve
0 = DC valve
1 = PWM
2 = On/Off
3 = 3-position
valve
0 = DC valve
0 = DC valve
1 = PWM
2 = On/Off
3 = 3-position
valve
A6V11917618_en--_b