3.2.3
Siemens Industry, Inc.
Building Technologies Division
X400
Pin
Designation
1
7_+
2
7_-
3
8_+
4
8_-
Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 A

NACs Configured as Shorting Device Inputs

NAC 5 through NAC 8 can be configured through configuration tool ZEUS as Short-
ing Device Inputs, i.e. for monitoring dry relay contacts. Wiring and configuration is
limited to Class B and these inputs can be configured as Supervisory, Status or
Trouble inputs. The input devices must be of shorting type.
X300
Pin
Designation
1
NAC5_+
2
NAC5_-
3
NAC6_+
4
NAC6_-
Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 AWG
X400
Pin
Designation
1
NAC7_+
2
NAC7_-
3
NAC8_+
4
NAC8_-
Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 AWG
Description
Positive feed for Auxiliary Circuit 7 (DC +24 V)
Return feed for Auxiliary Circuit 7 (DC -24 V)
Positive feed for Auxiliary Circuit 8 (DC +24 V)
Return feed for Auxiliary Circuit 8 (DC -24 V)
Description
Positive feed for Contact Input Circuit 1
Return feed for Contact Input Circuit 1
Positive feed for Contact Input Circuit 2
Return feed for Contact Input Circuit 2
Description
Positive feed for Contact Input Circuit 3
Return feed for Contact Input Circuit 3
Positive feed for Contact Input Circuit 4
Return feed for Contact Input Circuit 4
Model PAD-5-CLSA
1
NAC Circuits
A6V101030359_en--_c
13