JKSSS+ Series
1.2 Specifications (continued)
Two Stage Electronic
Overload Curves
Overload Reset
Retentive Thermal Memory
Dynamic Reset Capacity
Phase Current Imbalance
Protection
Over Current Protection
(Electronic Shear Pin)
Load Loss Trip Protection
Coast Down (Back Spin)
Lockout Timer
Starts-per-hour Lockout Timer
Type / Rating
Run Indication
At Speed Indication
Acceleration Adjustments
Dual Ramp Settings
Deceleration Adjustments
Jog Settings
Kick Start Settings
Fault Display
Lockout Display
Up to 60 Events
JKSSS+ Series - 2
Advanced Motor Protection
Starting: Programmable for Class 5 through 30
Run: Programmable for Class 5 through 30 when "At-Speed" is detected.
Manual (default) or automatic
Overload circuit retains thermal condition of the motor regardless of control
power status. Unit uses real time clock to adjust for off time.
Overload will not reset until thermal capacity available in the motor is enough
for a successful restart. Starter learns and retains this information by
monitoring previous successful starts.
Imbalance Trip Level: 5 - 30% current between any two phases
Imbalance Trip Delay: 1 -20 seconds
Trip Level: 100 - 300% of motor FLA
Trip Delay: 1 - 20 seconds
Under Current Trip Level: 10 -90 % of motor FLA
Under Current Trip Delay: 1 - 60 seconds
Coast Down Time Range: 1 - 60 minutes
Range: 1 - 6 successful starts per hour
Time between starts: 1 - 60 minutes between start attempts
Programmable Outputs
Form C (DPDT), Rated 5 amps 240 VAC max, (1200 VA)
Programmable
Programmable
Programmable Ramp Types: Voltage or Current Ramp (VR or CR)
Starting Torque: 0 - 100% of line voltage (VR) or 0 - 600% of motor FLA (CR)
Ramp Time: 1 to 120 seconds
Current Limit: 200 - 500% (VR or CR)
4 Options: VR1+VR2; VR1+CR2; CR1+CR2; CR1+VR2
Dual Ramp Control: Ramp 1 = Default
Ramp 2 = selectable via dry contact input
Begin Decel Level: 0 - 100% of line voltage
Stop Level: 0 to 1% less than Begin Decel Level
Decel Time: 1 - 60 seconds
Voltage Jog: 5 - 75%
Kick Voltage: 10 - 100%
Kick Time: 0.1 - 2 seconds
Shorted SCR, Phase Loss, Shunt Trip, Phase Imbalance Trip, Overload,
Overtemp, Overcurrent, Short Circuit, Load Loss, Undervoltage or Any Trip
Coast Down Time, Starts Per Hour, Time Between Starts, and Any Lockout
Event History
Data includes cause of event, time, date, voltage, power factor and current for
each phase and ground fault current at time of event
2.3 - 4.2KV