5.1.9 RTD Configuration (Setpoint Page 9)
Setpoint
Security
Page
Level
Use NEMA Temp for RTD Values
# of RTD Used for Stator
RTD Voting
Stator Phase A1 Type
RTD #1 Description
Stator Phase A1 Alarm Level
Stator Phase A1 Trip Level
Stator Phase A2 Type
RTD #2 Description
Stator Phase A2 Alarm
Stator Phase A2 Trip Level
Stator Phase B1 Type
RTD #3 Description
Stator Phase B1 Alarm Level
Stator Phase B1 Trip Level
Stator Phase B2 Type
RTD #4 Description
Stator Phase B2 Alarm Level
Stator Phase B2 Trip Level
Stator Phase C1 Type
RTD #5 Description
Stator Phase C1 Alarm Level
Stator Phase C1 Trip Level
Stator Phase C2 Type
RTD #6 Description
Stator Phase C2 Alarm Level
Stator Phase C2 Trip Level
End Bearing Type
RTD #7 Description
End Bearing Alarm Level
End Bearing Trip Level
Shaft Bearing Type
RTD #8 Description
Shaft Bearing Alarm Level
Shaft Bearing Trip Level
RTD #9 Type
RTD #9 Description
RTD #9 Alarm Level
RTD #9 Trip Level
JKSSS+ Series - 42
Factory Setting
Description
Disabled
4
Disabled
Off
Stator A1
Off
Off
Off
Stator A2
Off
Off
Off
Stator B1
Off
Off
Off
Stator B2
Off
Off
Off
Stator C1
Off
Off
Off
Stator C2
Off
Off
Off
End Bearing
Off
Off
Off
Shaft Bearing
Off
Off
Off
User defined
Off
Off
Default
Enabled or Disabled
0-6
Enabled or Disabled
120 OHM NI, 100 OHM NI, 100 OHM PT, 10
OHM CU
User defined, Up to 15 Characters
0-240C (32-464F), Off
0-240C (32-464F), Off
Same as Stator Phase A1
User defined, Up to 15 Characters
0-240C (32-464F), Off
0-240C (32-464F), Off
Same as Stator Phase A1
User defined, Up to 15 Characters
0-240C (32-464F), Off
0-240C (32-464F), Off
Same as Stator Phase A1
User defined, Up to 15 Characters
0-240C (32-464F), Off
0-240C (32-464F), Off
Same as Stator Phase A1
User defined, Up to 15 Characters
0-240C (32-464F), Off
0-240C (32-464F), Off
Same as Stator Phase A1
User defined, Up to 15 Characters
0-240C (32-464F), Off
0-240C (32-464F), Off
Same as Stator A1
User defined, Up to 15 Characters
0-240C (32-464F), Off
0-240C (32-464F), Off
Same as Stator Phase A1
User defined, Up to 15 Characters
0-240C (32-464F), Off
0-240C (32-464F), Off
Same as Stator Phase A1
User defined, Up to 15 Characters
0-240C (32-464F), Off
0-240C (32-464F), Off
2.3 - 4.2KV
Range
Section
SP9.1
SP9.2
SP9.3
SP9.4