5.1.3 Phase and Ground Settings (Setpoint Page 3)
Setpoint
Security
Page
Level
Imbalance Alarm Level
Imbalance Alarm Delay
Imbalance Trip Level
Imbalance Trip Delay
Undercurrent Alarm Level
Undercurrent Alarm Delay
Overcurrent Alarm Level
Overcurrent Alarm Delay
Overcurrent Trip Level
Overcurrent Trip Delay
Phase Loss Trip
Phase Loss Trip Delay
Phase Rotation Detection
Phase Rotation Trip Delay
*Ground Fault Alarm Level
*Ground Fault Alarm Delay
*Ground Fault Loset Trip Level
*Ground Fault Loset Trip Delay
*Ground Fault Hiset Trip Level
*Ground Fault Hiset Trip Delay
Overvoltage Alarm Level
Overvoltage Alarm Delay
Overvoltage Trip Level
Overvoltage Trip Delay
Undervoltage Alarm Level
Undervoltage Alarm Delay
Undervoltage Trip Level
Undervoltage Trip Delay
Line Frequency Trip Window
Line Frequency Trip Delay
P/F Lead P/F Alarm
P/F Lead Alarm Delay
P/F Lead P/F Trip
P/F Lead Trip Delay
P/F Lag P/F Alarm
P/F Lag Alarm Delay
P/F Lag P/F Trip
P/F Lag Trip Delay
Power Demand Period
KW Demand Alarm Pickup
KVA Demand Alarm Pickup
KVAR Demand Alarm Pickup
Amps Demand Alarm Pickup
* Ground fault option must be installed.
Factory Setting
Description
15% FLA
1.5 sec
20%
2.0 sec
Off
2.0 sec
Off
2.0 sec
Off
2.0 sec
Enabled
0.1 sec
ABC
1.0 sec
Off
0.1 sec
Off
0.5 sec
Off
0.008 sec
Off
1.0 sec
10%
2.0 sec
Off
1.0 sec
15%
2.0 sec
Disabled
1.0 sec
Off
1.0 sec
Off
1.0 sec
Off
1.0 sec
Off
1.0 sec
10 min
Off KW
Off KVA
Off KVAR
Off Amps
Default
5-30 %, Off
1.0-20.0 sec
5-30 %, Off
1.0-20.0 sec
10-90 %, Off
1.0-60.0 sec
100-300 %, Off
1.0-20.0 sec
100-300 %, Off
1.0-20.0 sec
Enabled or Disabled
0-20.0 sec
ABC, ACB or Disabled
1.0 - 20.0 sec
5-90 %, Off
0.1-20.0 sec
5-90 %, Off
0.1-20 sec
5-90 %, Off
0.008-0.250 sec
5 -30%, Off
1.0-30.0 sec
5-30%, Off
1.0-30.0 sec
5-30%, Off
1.0-30.0 sec
5-30%, Off
1.0-30.0 sec
0-6 Hz, Disabled
1.0-20.0 sec
0.1-1.00, Off
1-120 sec
.01-1.00, Off
1-120 sec
.01-1.00, Off
1-120 sec
.01-1.00, Off
1-120 sec
1 - 60 min
Off, 1-100000
Off, 1-100000
Off, 1-100000
Off, 1-100000
2.3 - 4.2KV
Range
Section
SP3.1
SP3.2
SP3.3
SP3.4
SP3.5
SP3.6
SP3.7
SP3.8
SP3.9
SP3.10
SP3.11
SP3.12
SP3.13
SP3.14
SP3.15
SP3.16
SP3.17
SP3.18
SP3.19
SP3.20
JKSSS+ Series - 37