JKSSS+ Series
Chapter 5 - Setpoint Programming
The JKSSS+ Series has thirteen programmable setpoint pages which define the
motor data, ramp curves, protection, I/O configuration and communications. In Section
5.1, the setpoint pages are outlined in chart form. In Section 5.2 the setpoint pages
are illustrated and defined for easy navigation and programming. Note: Setpoints can
only be changed when the starter is in the Ready Mode. Also the soft start will not start
when it is in programming mode.
5.1
Setpoints Page List
These charts list the Setpoint Page, the programmable functions and the section.
5.1.1 Basic Configuration (Setpoint Page1)
Setpoint
Security
Page
Level
Motor Full Load Amps (FLA)
Service Factor
Overload Class
NEMA Design
Insulation Class
Line Voltage
Line Frequency
5.1.2 Starter Configuration (Setpoint Page 2)
Setpoint
Security
Page
Level
Start Control Mode
Jog Voltage
Start Ramp #1 Type
Initial Voltage #1
Ramp Time #1
Current Limit #1
Initial Current #1
Ramp Time #1
Maximum Current #1
Start Ramp #2 Type
Initial Voltage #2
Ramp Time #2
Current Limit #2
Initial Current #2
Ramp Time #2
Maximum Current #2
Kick Start Type
Kick Start Voltage
Kick Start Time
Deceleration
Start Deceleration Voltage
Stop Deceleration Voltage
Deceleration Time
Timed Output Time
Run Delay Time
At Speed Delay Time
JKSSS+ Series - 36
Factory Setting
Description
Model dependent
1.15
10
B
B
Model dependent
60
Factory Setting
Description
Start Ramp 1
50%
Voltage
20%
10 sec
350% FLA
200% FLA
10 sec
350% FLA
Disabled
60%
10 sec
350 % FLA
200% FLA
10 sec
350% FLA
Disabled
65%
0.50 sec
Disabled
60%
30%
5 sec
Off
1 Sec
1 Sec
Default
50 - 100% of Unit Max Current Rating
(Model and Service Factor dependent)
1.00 – 1.3
O/L Class 5-30
A-F
A, B, C, E, F, H, K, N, S
1000 to 7200V
50 or 60 HZ
Default
Jog, Start Ramp 1, Start Ramp 2, Custom
Accel Curve, Start Disabled, Dual Ramp,
Tach Ramp
5-75%, Off
Current, Voltage
0-100%
0-120 sec
200-500 %
0-300%
0-120 sec
200-500 %
Current, Voltage, Disabled
0-100 %
0-120 sec
200-500 %
0-600 %
0-120 sec
200-500 %
Voltage or Disabled
10-100 %
0.10-2.00
Enabled or Disabled
0-100 %
0-59 %
1-60 sec
1-1000 sec, Off
1-30 sec, Off
1-30 sec, Off
2.3 - 4.2KV
Range
Section
SP1.1
SP1.2
SP1.3
SP1.4
SP1.5
SP1.6
SP1.7
Range
Section
SP2.1
SP2.2
SP2.3
SP2.4
SP2.5
SP2.6
SP2.7
SP2.8
SP2.9