TD Series
5.4.10 Fault History and Run Time
Fn
Group
F075
Fault History #1, Latest Fault
F076
Time Stamp, Fault #1
F077
Date Stamp, Fault #1
Fault History #2,
F078
Previous Fault
F079
Time Stamp, Fault #2
F080
Date Stamp, Fault #2
F081
Fault History #3, Oldest Fault
F082
Time Stamp, Fault #3
F083
Date Stamp, Fault #3
F084
Run Time, Hours
F085
Run Time, K Hours
F086
Run Counts
F087
Run Counts, 10K times
Digital Solid State Soft Starter 48 - 1250A
Function
0, 1 - 27 (Fault #: see Fault
code list; 0: No fault history)
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
01.01 - 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
0, 1 - 27 (Fault #: see Fault
code list; 0: No fault history)
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
01.01 - 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
0, 1 - 27 (Fault #: see Fault
code list; 0: No fault history)
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
01.01 - 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
000.0 - 999.9 (hours)
0000 - 9999 (thousand hours)
0000 - 9999 (times)
0000 - 9999 (10 thousand times)

5.5 Function Descriptions

The unit is set at the factory with typical starting characteristics that perform well
in most applications.
Note: Customer must program motor FLA (F001) for unit to operate.
5.5.1 Motor and Overload Function Descriptions
F001 = Motor FLA
Factory Setting = 0
Range = 50 - 100% of Unit Max. Current.
Set the value of this function to the motor nameplate Full Load Amps
(FLA). Adjustments for service factor are not necessary when
programming this function. (See note below). If the motor nameplate
FLA is not available, use typical values as shown in NEC, NEMA
standard MG-1 or other reputable third party source (motor manufacturer,
etc.).
Note:
To prevent adjusting the settings beyond the starter Max Amp rating, the range
of adjustment for the Motor Nameplate FLA will vary to reflect the Service
Factor as programmed into F002. At the default setting of 1.0SF, the full range
of adjustment from 50 - 100% of the Max Amp rating is available. For example
F002 = 1.15 to reflect a 1.15SF, the maximum FLA programmable into F001 will
be limited to 85% of the starter Max. Amp rating (100% - 15%).
Adjustment
Range
TD - Series
- 20 -
Setting
Factory
Increments
Setting
View Only
0
View Only
00.00 EST
View Only
01.01
View Only
0
View Only
00.00 EST
View Only
01.01
View Only
0
View Only
00.00 EST
View Only
01.01
View Only
0
View Only
0
View Only
0
View Only
0
Section
5.5.10
5.5.10
5.5.10
5.5.10
5.5.10
5.5.10
5.5.10
5.5.10
5.5.10
5.5.10
5.5.10
5.5.10
5.5.10