TD Series
5.4.4 Kick Start Mode Functions
Fn
Group
F022
Kick Start
F023
Kick Voltage
F024
Kick Time
5.4.5 Decel Mode Functions
Fn
Group
F025
Deceleration Ramp
F026
Begin Decel Level (BDL)
F027
Decel Shut Off Voltage
F028
Decel Ramp Time
F029
Reserved
5.4.6 Protection Features
Fn
Group
F030
Current Imbalance Trip
F031
Current Imbalance Trip %
F032
Current Imbalance Trip Delay
F033
Over Current / Shear Pin Trip
F034
Over Current / Shear Pin Trip %
F035
Over Current Trip Delay
F036
Under Current Trip
F037
Under Current Trip %
F038
Under Current Trip Delay
F039
Coast Down Lockout Timer
F040
Coast Down Lockout Time
F041
Starts per Hour Lockout
F042
Maximum Starts per Hour
F043
Time Between Starts Lockout
F044
Minimum Time Between Starts
F045
Coast Down Timer Value
F046
Starts per Hour Timer Value
F047
Starts per Hour Count Value
F048
Time Value Between Starts
F049
Thermal Capacity to Start
Digital Solid State Soft Starter 48 - 1250A
Function
0=Disabled
1=Enabled
10 - 100%
0.1 - 2 Seconds
Function
0=Disabled / Coast to Stop
1=Enabled (except in event of OL Trip)
2=Enabled (continued Decel on OL Trip)
0 - 100 %
0 to (BDL minus 1)%
1 - 60 Seconds
Reserved
Function
0=Disabled
1=Enabled
5 - 30%
1 - 20 seconds
0=Disabled
1=Enabled
50 - 300% (note1)
1 - 20 seconds
0=Disabled
1=Enabled
10 - 90% (note1)
1 - 60 seconds
0=Disabled
1=Enabled
1 - 60 minutes
0=Disabled
1=Enabled
1 - 10
0=Disabled
1=Enabled
1 - 60 minutes
1 - 3600 Seconds
1 - 3600 Seconds
1 - 10 Starts
1 - 3600 Seconds
0 - 100 % Thermal Capacity
Adjustment
Range
Adjustment
Range
Adjustment
Range
TD - Series
- 18 -
Setting
Factory
Increments
Setting
1
0 (Disabled)
1%
65%
0.1 second
0.8 seconds
Setting
Factory
Increments
Setting
1
0 (Disabled)
1%
60%
1%
30%
1 second
10 seconds
Reserved
Reserved
Setting
Factory
Increments
Setting
1
0 (Disabled)
1%
10%
1 second
2 seconds
1
0 (Disabled)
1%
125%
1 second
1 second
1
0 (Disabled)
1%
40%
1 second
2 seconds
1
0 (Disabled)
1 minute
5 minutes
1
0 (Disabled)
1
2
1
0 (Disabled)
1 minute
15 minutes
View Only
0
View Only
0
View Only
0
View Only
0
View Only
0
Section
5.5.4
5.5.4
5.5.4
Section
5.5.5
5.5.5
5.5.5
5.5.5
5.5.5
Section
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6
5.5.6