95-10330_IF-800 V2016-10-20 Outdoor Terminal
IF-80x Outdoor Terminal
1 IF-800 Outdoor / IF-801
We are pleased that you have decided to use a terminal of
the IF-80x series for recording access data.
Scope of delivery:
IF-80x terminal (slave)
I/O controller board for controlling locking devices
Material for fastening
8-pin terminal strip
Blue wire for grounding the back panel
Mortise lock
Plastic strips for sealing the mortise lock
Please check the completeness and condition of the
shipment upon receipt.
2 Function of the IF-80x Terminal
Terminals of the IF-80x series are part of an access control system. They are preferably installed directly
next to locking devices. They are generally connected to a master terminal, access manager or terminal
controller via an RS485 data cable. These terminals are designed for controlling the access of persons, who
identify themselves with RFID credentials, as well as for controlling and monitoring locking devices.
We recommend:
installing a separate, fuse-protected circuit.
keeping a minimum distance of 30 cm between the terminal and other systems with RFID readers.
keeping a distance of 10 cm between connecting cables and power lines.
3 Danger Due to Electric Current
Electric shock can cause severe injuries or death.
De-energize the device.
Please observe the accident prevention regulations and take all precautionary measures
to ensure the safe installation of the devices.
Connection to power supply voltage and initial operation may therefore only be carried out by people
trained in electrical engineering.
The electrical installation, in which the device is to be operated, must comply with national standards. To
guarantee trouble-free operation, we recommend carrying out the electrical installation according to the
principles of a TN-S system, which means using separate neutral and grounding conductors.
Secure the power cable with a strain relief.
The device must be equipped with an external separator to ensure that the device can be de-energized.
The device must be equipped with an external fuse protection with a maximum nominal current of 16 A.
Interflex Datensysteme GmbH
1/13

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IF-80 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Interflex IF-80 Series

  • Page 1 The device must be equipped with an external separator to ensure that the device can be de-energized.  The device must be equipped with an external fuse protection with a maximum nominal current of 16 A.  Interflex Datensysteme GmbH 1/13...
  • Page 2: Intended Use

    Patch cable from PC to switch or hub RS485 data cable from an IF-4070 controller to an I/O controller board Please refer to the table "Function of Cables and Cable Types" for detailed information on the cable lengths, cable types and their diameters. Interflex Datensysteme GmbH 2/13...
  • Page 3 Ethernet/patch cable from switch/hub to controller/master max. 100 m Category 5 terminal Shielded cable from IF-80x terminal to controller/master max. 100 m J-Y(ST) Y 4x2x 0.6 mm terminal RS485 bus cable max. 1200 m J-Y(ST) Y 4x2x 0.6 mm Interflex Datensysteme GmbH 3/13...
  • Page 4 10. Screw down the IF-800 Outdoor/IF-801 terminal on the bottom left side (11) using the M2x6 countersunk screw included in the delivery. 11. Insert the mortise lock on the bottom right side and lock the IF-800 Outdoor/IF-801 terminal (13). 12. Use the enclosed plastic strips to seal the mortise lock. Interflex Datensysteme GmbH 4/13...
  • Page 5 Vertical mounting option with DIN appliance case Alternative mounting hole for wall-mounted cable Mounting holes for US standard inserted from the bottom Cable gland Hole for adjusting the reader Horizontal mounting option with DIN appliance case Foam rubber Interflex Datensysteme GmbH 5/13...
  • Page 6 8 The blue wire and the PE wire from the I/O controller board insulation. are connected to terminal 8 on the terminal strip. 7 The blue wire is connected to the strain relief. 9 Terminal strip Interflex Datensysteme GmbH 6/13...
  • Page 7 6.6 Important Points to Note Regarding the Mounting Please observe the following when mounting the terminal: Do not make any changes to the back panel. Fastening elements in other places can collide with the circuit board. Interflex Datensysteme GmbH 7/13...
  • Page 8 Ensure short cable routing. Cable loops can damage the device due to mechanical stresses. Tighten the screw only slightly or leave it out. Tightening the screw too tightly can result in mechanical stresses which can damage the device. Interflex Datensysteme GmbH 8/13...
  • Page 9 1 on the second I/O control board must be removed. BR2: With bridge 2, the switching contacts of the relay are changed from NO to NC.  BR3: Instead of bridge 3, an anti-tamper switch can be connected.  Interflex Datensysteme GmbH 9/13...
  • Page 10 OFF (not required if connected to a master terminal) Address 2 Address 3 Address 4 Address 5 Address 6 Address 7 Address 8 There is a four-way DIP switch on the I/O controller board for setting the hardware address. Interflex Datensysteme GmbH 10/13...
  • Page 11 After approximately 10 seconds, the terminal is ready for operation and can be checked via the cfg command. Make sure that an address is not used twice. The address must be within the address range of the controller (IF-4070).  Interflex Datensysteme GmbH 11/13...
  • Page 12: Initial Operation

    M2x6 countersunk screw included in delivery. Define the terminal in your time & attendance/access control software, e.g. IF-6020 or IF-6040. Check the device using a Mifare or LEGIC credential (depending on the order). Interflex Datensysteme GmbH 12/13...
  • Page 13: Technical Specifications

    The owner can dispose of the device himself or return it to the supplier. Copyright © 2016 Version Date: October 31, 2016 Interflex Datensysteme GmbH Zettachring 16, D-70567 Stuttgart, Germany Tel.: +49 (0711) 1322 0 Internet E-Mail: interflex.info@allegion.com Websites: www.interflex.de www.allegion.com...

This manual is also suitable for:

If-800If-801

Table of Contents