2-Wire Smoke Wiring (D125B) - Bosch B6512 Installation Manual

Hide thumbs Also See for B6512:
Table of Contents

Advertisement

Control panels
Callout ᅳ Description
5 ᅳ 1.8 kΩ EOL resistor (P/N: F01U009011) (included with the module)
6 ᅳ Smoke reset wire
7.4

2-wire smoke wiring (D125B)

PTC2
R2
R21
R9
R10
R8
TB1/J1
D125B
1
2
3
SWITCH
ZONE
ZONE
POWER
B
A
Callout ᅳ Description
1 ᅳ Switched auxiliary power from Output A (NC)
control panel
2 ᅳ Connection from an on-board point on the control
panel to Zone B
3 ᅳ Connection from an on-board point on the control
panel to Zone A
4/5 ᅳ Connection to common on the control panel (one
connection only)
6 ᅳ Supervised smoke detector to B LOOP negative
1
You can also use Output B or C in conjunction with a D133 or D134 relay module.
Bosch Security Systems B.V.
PTC1
R14
U1
RV1
RV4
RV3
4
5
6
7
8
9
10
PANEL
B-
A-
B+
A+
EARTH
COMMON
LOOP
LOOP
LOOP
LOOP
GND
R1
R11
R12
R22
RV2
18VAC
+ BAT -
Callout ᅳ Description
1 of
of the
7 ᅳ Supervised smoke detector to A LOOP negative
8 ᅳ Supervised smoke detector to B LOOP positive
9 ᅳ Supervised smoke detector to A LOOP positive
10 ᅳ Earth ground
11 ᅳ Output A jumper (under cover) set to AUX PWR
UL Installation manual
System wiring diagrams | en
NO C NC
COM AUX
R
Y
G
B
1
C
O
M
2
3
COM
4
5
COM
OUTPUT A
PWR A
B COM
\
2019-12 | 10 | F.01U.287.185
25
7 COM 8
6
7
C
O
M
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

B5512B4512B3512B5512eB4512eB3512e

Table of Contents