Control panels
Notice!
There can only be a difference of 2 volts (maximum) between the AUX power terminals of the
control panel or power supply and the device for the modules and keypads to work properly
under all conditions.
Maximum cable lengths
Follow these rules when wiring the SDI2 bus:
Cable capacitance
pF/ft
< 17
18
19
20
21
22
23
24
25
26
Table 7.1: Maximum cable length
Notice!
Use unshielded cable only.
Maximum capacitance of 140nF (140,000 pF) per system. Contact the wire manufacturer for
the capacitance ratings of the wire being used.
Bosch Security Systems B.V.
The SDI2 bus requires the use of unshielded cable from 12 AWG to 22 AWG (0.65 mm to
2 mm).
Refer to the SDI2 device or keypad documentation for the allowable maximum distance
from the control panel.
Maximum overall cable lengths are listed in the following table:
Overall cable length
ft
m
7500
2286
7500
2286
7350
2240
7000
2134
6666
2032
6363
1939
6086
1855
5800
1768
5600
1707
5385
1641
Cable capacitance
pF/ft
27
28
29
30
31
32
33
34
35
36
UL Installation manual
System wiring diagrams | en
Overall cable length
ft
m
5185
1580
5000
1524
4828
1472
4700
1433
4516
1376
4400
1341
4242
1293
4100
1250
4000
1219
3800
1158
2019-12 | 10 | F.01U.287.185