Nibe F1255 Installation Manual page 53

Ground source heat pump
Hide thumbs Also See for F1255:
Table of Contents

Advertisement

start delta-T, stop delta-T: Here, you can set the temper-
ature difference between solar panel and solar tank at
which the circulation pump will start and stop.
max. tank temperature, max. solar collector temp.: Here,
you can set the maximum temperatures in the tank and
solar panel respectively at which the circulation pump
will stop. This is to protect against excess temperatures
in the solar tank.
If the unit has an anti-freeze function, solar panel cooling
and/or passive/active recharging you can activate them
here. When the function has been activated, you can
make settings for them. "solar panel cooling", "passive
recharging" and "active recharging" cannot be combined,
only one function can be activated.
freeze protection
anti-freeze temperature: Here, you can set the temper-
ature in the solar panel at which the circulation pump is
to start to prevent freezing.
solar panel cooling
start solar collector cooling: If the temperature in the
solar panel is higher than this setting, at the same time
as the temperature in the solar tank is higher than the
set maximum temperature, the external function for
cooling is activated.
passive recharging
activation temperature: If the temperature in the solar
panel is higher than this setting, the function is activated.
However, the function is blocked for an hour if the
temperature of the brine entering the heat pump (BT10)
is higher than the set value for "max brine in" in menu
5.1.7.
deactivation temperature: If the temperature in the solar
panel is lower than this setting, the function is deactiv-
ated.
active recharging
activating dT: If the difference between the temperature
in the solar panel (BT53) and the temperature of the
brine entering the heat pump (BT10) is greater than this
setting, the function is activated. However, the function
is blocked for an hour if the temperature of the brine
entering the heat pump (BT10) is higher than the set
value for "max brine in" in menu 5.1.7.
deactivating dT: If the difference between the temper-
ature in the solar panel (BT53) and the temperature of
the brine entering the heat pump (BT10) is lower than
this setting, the function is deactivated.
See the accessory installation instructions for function
description.
NIBE F1255
MENU 5.3.6 - STEP CONTROLLED ADD. HEAT
start diff additional heat
Setting range: 0 – 2000 DM
Default values: 400 DM
diff. between additional steps
Setting range: 0 – 1000 DM
Default values: 100 DM
max step
Setting range
(binary stepping deactivated): 0 – 3
Setting range
(binary stepping activated): 0 – 7
Default value: 3
binary stepping
Setting range: on/off
Factory setting: off
Make settings for step controlled addition here. Step
controlled addition is for example an external electric
boiler.
It is possible, for example, to select when the additional
heat is to start, to set the maximum number of permit-
ted steps and whether binary stepping is to be used.
When binary stepping is deactivated (off), the settings
refer to linear stepping.
See the accessory installation instructions for function
description.
MENU 5.3.8 - HOT WATER COMFORT
activating the mixing valve
Setting range: on/off
Factory setting: off
outgoing hot water
Setting range: 40 - 65 °C
Default value: 55 °C
mixing valve amplifier
Setting range: 0.1 – 10.0
Default value: 1.0
mixing valve step delay
Setting range: 10 – 300 s
Default values: 30 s
Make settings for the hot water comfort here.
See the accessory installation instructions for function
description.
Chapter 8 | Control - Menus
53