Nibe F1255 Installation Manual page 51

Ground source heat pump
Hide thumbs Also See for F1255:
Table of Contents

Advertisement

MENU 5.3.1 - FLM
continuous pump op.
Setting range: on/off
Factory setting: off
pump speed
Setting range: 1 – 100%
Factory setting: 100%
time between defrosts
Setting range: 1 – 30 h
Default value: 10 h
months btwn filter alarms
Setting range: 1 – 12
Default value: 3
activate cooling
Setting range: on/off
Factory setting: off
continuous pump op.: Select for continuous operation
of the circulation pump in the exhaust air module.
pump speed: Set the desired speed for the circulation
pump in the exhaust air module.
time between defrosts: Here, you can set the minimum
time that must pass between defrosts of the heat ex-
changer in the exhaust air module.
When the exhaust air module is in operation the heat
exchanger is cooled so that ice builds up on it. When
too much ice builds up the heat transfer capacity of the
heat exchanger is reduced and defrosting is required.
Defrosting warms up the heat exchanger so that the ice
melts and runs off via the condensation hose.
months btwn filter alarms: Here, you can set how many
months should pass before the heat pump notifies that
it is time to clean the filter in the exhaust air module.
Clean the exhaust air module's air filter regularly, how
often depends on the amount of dust in the ventilation
air.
activate cooling: Here, you can activate cooling via the
exhaust air module. When the function has been activ-
ated, the cooling settings are displayed in the menu
system.
TIP
See the accessory installation instructions for
function description.
NIBE F1255
MENU 5.3.2 - SHUNT CONTROLLED ADD.
HEAT
prioritised additional heat
Setting range: on/off
Factory setting: off
start diff additional heat
Setting range: 0 – 2000 DM
Default values: 400 DM
minimum running time
Setting range: 0 – 48 h
Default value: 12 h
min temp.
Setting range: 5 – 90 °C
Default value: 55 °C
mixing valve amplifier
Setting range: 0.1 –10.0
Default value: 1.0
mixing valve step delay
Setting range: 10 – 300 s
Default values: 30 s
Set when the addition is to start, the minimum run time
and the minimum temperature for external addition with
shunt here. External addition with shunt is for example
a wood/oil/gas/pellet boiler.
You can set shunt valve amplification and shunt valve
waiting time.
Selecting "prioritised additional heat" uses the heat from
the external additional heat instead of the heat pump.
The shunt valve is regulated as long as heat is available,
otherwise the shunt valve is closed.
TIP
See the accessory installation instructions for
function description.
MENU 5.3.3 - EXTRA CLIMATE SYSTEM
use in heating mode
Setting range: on/off
Factory setting: on
use in cooling mode
Setting range: on/off
Factory setting: off
Chapter 8 | Control - Menus
51