Command Parameters - Toshiba XLTR-200 Instruction Manual

Toshiba serial multiprotocol network gateway user's manual
Table of Contents

Advertisement

13.7.1 Command Parameters

Parameter
Bit
0001
word
Frequency command
0002
0
RUN command
1
Reserved
2
Forward • reverse run
selection
3
Acc/dec #1 / #2
selection
4
Reserved
5
Reserved
6
Reserved
7
Jog mode selection
8
Feedback control
9
Compulsory DC
injection braking mode
A
Fundamental
parameter switching
B
Gate block command
(coast stop command)
C
Emergency off
command
D
Reset command
(trip clear)
E
Reserved
F
Reserved
0003
word
RS232 command /
frequency selection
0004
word
Preset speed run
command
Function
Bank
0
0
0
0
Mask
Adjustment Range
FFFF
0.00 ∼ 400.00Hz
Actual frequency will be limited by
LL, UL and Fmax.
0: Stop
1: Run
0: reverse
1: forward
0: Acc / dec #1
1: Acc / dec #2
0: Normal (acc/dec mode)
1: Jog mode
0: Feedback valid
1: Feedback invalid
0: No compulsory DC injection
braking
1: Compulsory DC injection
below DC INJECTION
START FREQUENCY
0: V/F #1
1: V/F #2
0: Normal
1: Gate block
0: Does nothing
1: Emergency off
0: Does nothing
1: Reset
0003
0000: FREQUENCY MODE
SELECTION, COMMAND
MODE SELECTION
settings
0001: RS232C commands valid
0002: RS232C frequency valid
0003: RS232C commands and
frequency valid
000F
0000: Output frequency
selected by FREQUENCY
MODE SELECTION
0001 ∼ 000F: speeds 1 ∼ 15
64
Multiplier
0.01

Advertisement

Table of Contents