Metasys N2 Point Attributes
Edit Object Type: Menu selection 1 allows modification of the object
type. Figure 18 shows an example of how to change the current
setting of AI to AO.
Edit Object Number: Menu selection 2 allows modification of the
object number. The current configuration as indicated in Figure 18
shows that point #1 is configured to be AI #1.
Edit Multiplier: Menu selection 3 allows modification of the multiplier
to be used with analog (AI or AO) objects. This setting has no effect
when the point is configured to be a binary (BI or BO) object.
Edit Bit Mask: Menu selection 4 allows modification of the bit mask
to be used with binary (BI or BO) objects. This setting has no effect
when the point is configured to be an analog (AI or AO) object. Note
that the bit mask is displayed and entered as a hexadecimal value
(e.g. to mask bits #15 and #10, a value of "8400" must be entered).
Figure 18: Edit Metasys N2 Attributes