Toshiba XLTR-200 Instruction Manual page 48

Toshiba serial multiprotocol network gateway user's manual
Table of Contents

Advertisement

slave. This gateway follows this generally-accepted industry paradigm,
where a point's configured Modbus master "register" value is decremented
by 1 before it is placed "on the wire". Some vendors, however, will
document their slave device's "addressed as" values in their literature,
which means that these register indices must have 1 added to them when
entered into the gateway's "Modbus master register" field.
For example, the Toshiba VF-AS1 drive's Modbus RTU slave protocol
implementation & corresponding user's manual references all internal ASD
parameters using "addressed as" values. This means that (in addition to
the required conversion from Toshiba's native hexadecimal radix to the
Modbus protocol's natural decimal radix) these parameter values must
have 1 added to them when they are to be accessed via an ICC gateway
executing the Modbus RTU master protocol.
e.g VF-AS1 "command 1" parameter is documented to be FA00 in the
Toshiba literature. Converting this to decimal, we arrive at a value of
64000. To allow a point in the gateway's database to correctly access the
"command 1" parameter via Modbus RTU, therefore, that point's Modbus
master "register" attribute must be set to 64001 (which will result in an
address value of 64000 (0xFA00) "on the wire").
47

Advertisement

Table of Contents
loading

Table of Contents