A
Power Cable Specifications
YJV 5-core cables are recommended. When the ambient temperature is 40º C, the conductor
working temperature cannot exceed 90º C.
For the installation torque for power connection of involved electrical parts, see the specifications of
the electrical parts. If the torque is not specified, see the torque requirements listed in the following
table.
Rated
Wiring Terminal
Current (A)
160
250
Power input (L/N)
400
630
160
250
Power input (PE)
400
630
< 10
10 ≤ I ≤ 40
AC output (L)
40 < I ≤ 63
< 10
10 ≤ I ≤ 40
AC output (N/PE)
40 < I ≤ 63
Recommended
Terminal/Bolt
Cable Diameter
Specifications
2
(mm
)
50
DT-M10
95
DT-M12
185
DT-M16
2 x 185
DT-M16
25
DT-M10
50
DT-M10
95
DT-M12
2 x 95
DT-M12
2.5
Cord end terminal
(crimping screw
specification: M4)
6
Cord end terminal
(crimping screw
specification: M4)
10
Cord end terminal
(crimping screw
specification: M4)
2.5
OT-M6
6
OT-M6
10
OT-M6
12
Recommended
Torque (N•m)
27
47
120
120
27
27
47
47
1.2
1.2
1.2
4.5
4.5
4.5

Advertisement