• Only trained and qualified personnel are allowed to install, operate, and maintain the equipment. • Only personnel certified or authorized by Huawei are allowed to replace or change the equipment or components (including software). • Any fault or error that might cause safety problems must be reported immediately to a supervisor.
Page 3
Overview 1. Appearance dimensions of the PDU5000. Unit: mm Back Front 482.6 2. Feature Introduction of the PDU5000. Front view of the PDU5000 Back view of the PDU5000 Component Name Component Name Surge protective device (SPD) AC input circuit breaker...
Page 4
B10A/1 P L,N,PE RVVZ-3x1.0 QF10 B10A/1 P L,N,PE RVVZ-3x1.0 QF11 B10A/1 P L,N,PE RVVZ-3x1.0 FS/20K A C32A/2 P 2. Install cables for the PDU5000 by referring to the following figure. AC Output AC Input Output PE Input PE Equipment room PE...
2. Turn on the external power input circuit breaker. 3. Turn on the input switch. 4. Turn on all output circuit breakers of the PDU5000 in sequence and check that the output voltage is normal by using a multimeter. 5. After checking that the parameters are normal, turn off all the circuit breakers one by one and disconnect the power supply.
The switch trips abnormally. device power input check whether the system is overloaded. • The PDU5000 is faulty. • is abnormal. Restart the PDU5000. If the PDU5000 is faulty, replace it. • The PDU5000 The output power cable is • does not report not securely connected.
≤ 2000 m Altitude Rated operating frequency 50 Hz Rated operating voltage 220 V AC Installation mode Installed inside a cabinet Protection level IP20 Huawei Technologies Co., Ltd. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China www.huawei.com...