3-8 Installing the Controller Link Interface Unit
This section describes the method for installing and wiring the Controller Link Interface Unit,
which can be mounted to an NS10 or NS12 PT. The Controller Link Interface Unit cannot be
mounted to an NS8 or NS5 PT.
3-8-1
Controller Link Interface Unit Components
The following table shows the Controller Link Interface Unit's product configuration.
Model
NS-CLK21
Controller Link
Interface Unit
Reference
Note
Name
NS-CLK001 Con-
nector Conver-
sion Board (1)
NS-CLK01 Con-
troller Link Sup-
port Board (1)
Connector (1)
Cover (1)
Cable (1)
Screw (M3) (10)
Instruction sheet
NS-CLK21 Units with lot number 12Y2 or later (manufactured on November 12, 2002
or later) comply with EC Directives.
To comply with EC Directives (Low Voltage Directive) when mounting the Controller Link Inter-
face Unit on the PT, attach the PT to a control panel that has been cut to fit to size. (Refer to
3-1-3 Mounting the PT to the Control Panel for cutout dimensions.)
3-8 Installing the Controller Link Interface Unit
Components
Contents
Used for mounting the Controller Link
Support Board to the PT.
Connects the PT to the Controller Link
Network.
Connects the communications cable
and Controller Link Support Board.
Protects the connector and the Con-
troller Link Support Board.
Connects the cover and the PT's func-
tional ground terminal to prevent
noise.
These screws are used for:
Securing the Connector Conversion
Board to the back of the PT.
Securing the cover to the back of
the PT.
Attaching the cable to the cover.
Instruction sheet for NS-CLK21
3-39