4-2 1:N Host Connection
Connecting to CS-series Serial Communications Boards
Serial Communications Boards with RS-232C and RS-422A Ports for Use with CS-series
CPU Units:
Setting DM Area Allocations in CPU Unit
Write the settings directly from the Programming Device or Support Software (Programming
Console or CX-Programmer) to the DM Area (Parameter Area) in the CPU Unit. After writing
the settings, enable the settings by turning ON the power again, restarting the Unit, restarting
the communications port, or executing the CHANGE SERIAL PORT SETUP (STUP) instruc-
tion.
The following table shows the allocated DM Area words and settings.
The allocations and settings are the same for RS-232C and RS-422A (CS1W-SCB41 Port 2).
Allocated DM Area words
Port 1
DM32000
DM32001
DM32006
Note 1. Set the baud rate to a numeric value between 0000 to 0009 Hex. (The setting is the same for
2. When using a 1:N connection, set the value for @ to 1 or higher.
For example, to connect PTs with unit numbers 3 to 6 to Port 1 in 1:N NT Links, set DM32000
to 8200 Hex, DM32001 to 0000 Hex, and DM32006 to 0006 Hex.
Reference
4-12
CS1W-SCB21 (Both ports 1 and 2 are RS-232C ports.)
CS1W-SCB41 (Port 1 is an RS-232C port and Port 2 is an RS-422A port.)
Port 2
DM32010
DM32011
DM32016
any value between 0000 and 0009 Hex.)
When setting a 1:N NT Link in the CX-Programmer, set the baud rate to 38,400 bps.
Write value
8200
1:N NT Link Mode
0000 to 0009
Baud rate (normal)
(See note 1.)
000@
@: Largest unit number (1 to 7) of the
connected PTs. (See note 2.)
Settings