Engineering tools installed (»Engineer«), screenshots in this documentation may differ from the representation on the screen. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 5
The information given in this documentation is valid for the following devices: Product series Type designation Version Inverter Drives 8400 motec E84DGFCRxNx PROFINET PROFINET Communication Unit E84DGFCRxJx PROFINET + Safety Features and variants ( 12) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Response of the outputs in compliance with PROFINET standard V2.3 ( 38) • Updated: LED status displays ( 66) 11/2011 TD17 General revision 06/2011 TD17 First edition Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Optically highlighted reference to another page. It is activated with a mouse-click in this online documentation. Step-by-step instructions Step-by-step instructions are indicated by a pictograph. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
PROFINET® (Process Field Network) is a real-time capable fieldbus system based on Ethernet. PROFINET® is a registered trademark and patented technology licensed by the PROFIBUS & PROFINET International (PI) user organisation. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Pictograph Signal word Meaning Note! Important note to ensure trouble-free operation Tip! Useful tip for easy handling Reference to another document Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• who have the corresponding qualifications for their work. • who know and can apply all regulations for the prevention of accidents, directives, and laws applicable at the place of use. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Observe the safety instructions and application notes contained in this manual. Residual hazards Device protection • The Communication Unit contains electronic components that can be damaged or destroyed by electrostatic discharge. ( 19) Installation Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
E84DGFCRFJP IP 65 3× DI 2× DI 1× DO 1× AI E84DGFCREJP IP 65 3× DI 2× DI 1× DO 1× AI Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 13
Reference manual/online help for the Inverter Drive 8400 motec Here you will find detailed information on how to configure the safety system (safety option). Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Plug connector for wiring PROFINET port 1 at A2 Plug connector for wiring PROFINET port 2 at A3 Plug connector for the wiring of the LEDs to A1 Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 15
• Wire the M12 connectors or cable glands used to the corresponding contacts of the terminal strips/plug connectors X3, X4 and X61. "Inverter Drives 8400 motec" hardware manual Observe the notes and wiring instructions contained in this documentation. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• U = 24 V DC (20 V - 0 % ... 29 V + 0 %) • I = 120 mA Conformities, approvals • CE • UR / cUR (see also hardware manual) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• Some codes may require a longer processing time (see reference manual/ online help for Inverter Drive 8400 motec). There are no interdependencies between parameter data and process data. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
The use of external switches can also lead to runtime delays. Depending on the system constellation, it may be useful to create a star topology or a line/mix topology. Network topology ( 21) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• Fieldbus communication is not possible or faulty. • I/O signals are faulty. • The safety function is faulty. Protective measures • Discharge electrostatic charges before touching the Communication Unit. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Legend for fig. [5-1] Drive Unit Communication unit Wiring Unit Cover of the Drive Unit EDK84DG... Mounting instructions of the Drive Unit, Communication Unit, Wiring Unit Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
The combination of a line and a stub is useful for system wiring. PROFINET supports the following topologies: • Switch / star E94YCER005 [5-2] Switch / star topology (S = switch, D = I/O device) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Data line (transmitted data, plus) Rx + Data line (received data, plus) Tx - Data line (transmitted data, minus) Rx - Data line (received data, minus) not assigned Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• Access to parameters of a device that is disconnected from the mains is not possible. "Inverter Drives 8400 motec" hardware manual Here you can find detailed information on how to wire the Communication Unit. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Stop! Before switching on the inverter for the first time, check the entire wiring with regard to completeness, short circuit, and earth fault. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
0 ... 4 bytes Example of selecting the device data base file • "PCD (8W)" = 8 process data words in slot 1 of the PROFINET telegram Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• "n.n.n.n" (n = 0 ... 999) • "port-xyz" (x, y, z = 0 ... 9) • "port-xyz-abcde" (a, b, c, d, e, x, y, z = 0 ... 9) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 28
• Then click Accept change. The station name is saved and written to code C13899. • In the Lenze setting a deleted name is displayed. The name is also deleted if the "Reset to factory defaults" command is executed by an IO supervisor or an I/O controller.
• In the case of impermissible settings, the red LED BE blinks (LED status displays ( 66) and the error message PROFINET: Stack init error [0x01bc6534] is output. ( 74) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
1. Execute the menu command Online Profinet configurator addresses..The Assign IP addresses dialog window is opened, and all Lenze PROFINET devices connected are listed. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 31
4. With the C00002 = "11: Save all parameter sets" device command, the current IP configuration is saved non-volatilely. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 33
• If the gateway address and the IP address are identical, gateway functionality is not used. • DHCP is not supported. • The gateway address is set/changed in C13002. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
For an online connection between the »Engineer« and the inverter, the inverter must have an IP address (see Setting the IP configuration ( 29) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 35
• Select the device access path to the desired inverter by clicking Find. After having established the online connection, you can continue work with the »Engineer« as usual. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• Addressing the inverter requires a valid IP configuration if communication between the PC/ »Engineer« and the inverter via PROFINET is to be established. Setting the IP configuration ( 29) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• The acyclic channel provides access to all Lenze codes. • Parameter changes must be stored via code C00002 of the Inverter Drive 8400 motec. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
The output data are treated according to the parameter setting of codes C13880/1, C13881/0, and C13885/0. Invalid IO controller output values The output data are set to '0'. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Reference manual/online help for the Inverter Drive 8400 motec Here you will find detailed information on the port/function block interconnection in the »Engineer« and the port blocks. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
1. Go to the Process data objects tab and click Go to application. 2. The Ports tab displays the port blocks MCI_IN and MCI_OUT. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 42
Assignment Signal --> Function Block dialog window. Select the signals and then confirm the selection with OK. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 43
Select the signals and then confirm the selection with OK. The current interconnection is only displayed if the following has been set for the control mode in code C00007 = 40: Network (MCI/CAN). Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
1 (TRUE) Data in word 1/2 are valid. Connection status of the 0 (FALSE) Inverter is offline ("stay-alive" operation) inverter 1 (TRUE) Inverter is online Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
An I/O controller can always be used to request parameters from an I/O device if the I/O device is in the "Data_Exchange" state. E94YCER010 [9-1] Data communication via the acyclic channel Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• After parameter processing, the parameter request is completed by transmitting the parameter response in the form of a "Read.res (+)" to the I/O controller. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• Number of requested subindices. (If there is more than one subindex, only the parameter value is repeated.) • In the case of string codes, the number of characters is entered here. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 50
Byte 7 Byte 8 Byte 9 Byte 10 Value Field Data type Values Value String 0x00 ..0xFF 0x0000 ..0xFFFF 0x0000 0000 ..0xFFFFFFFF Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 53
Error code without additional information Byte 7 Byte 8 Error code High byte Low byte For the meaning see the chapter "Error information (error)" ( 61) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Mirrored value of the parameter request Response identification 0x01: Parameter written Axis 0x00 or 0x01 Number of indices 0x"n" (n = number of parameters requested) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• Error code with additional information (number of values = 0x02) A faulty access to a parameter "n" is indicated at the nth position in the response frame of a multi-parameter request. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 58
Low byte High byte Low byte Field Data type Values Error code 0x0000 ..0xFFFF Error information (error) ( 61) Additional information (if available) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Low word: low byte 0x00 0x00 0x00 0x32 Value to be written = 0.05 [s] x 1000 (internal factor) = 50 = 0x00 00 00 32 Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 60
Error code without additional information Byte 7 Byte 8 Error code High byte Low byte For the meaning see the chapter "Error information (error)" ( 61) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Write request: Number of values of the parameter consistent data do not match the number of subindices in the parameter address 0x0019 Reserved 0x0064 Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
2. The I/O controller only writes a complete data set into the DPM. Configuring consistent data Note! Consistency is achieved by an appropriate I/O controller configuration (see documentation for the configuring software). Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• The monitoring time elapses when the "Data_Exchange" status is exited. After this response delay has elapsed, the response set is executed with the error message "PROFINET: Data_Exchange status quit [0x01bc6531]" ( 73) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
• The Communication Unit reports a connection interruption to the IO controller and changes to the "No_Data_Exchange" state. • The error message "PROFINET: Exist. conn. to 8400 lost [0x01bc3100]" is output. ( 71) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
No communication (the Communication Unit is not active on the fieldbus or is in the "Init" status). (bus status) blinking Communication active (the Communication Unit is in the "Data_Exchange" status.) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 67
500 ms blinking pattern: The "Node blinking test" PROFINET function is activated by the I/O controller. The jittering LED serves to identify/localise accessible I/O devices. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Instance ID Module ID Error ID Reference manual/online help for the Inverter Drive 8400 motec Detailed information on the error codes is provided here. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Remedy Parameter could not be written. • Download application again (including module). • Send the device and a description of the fault to Lenze. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 72
Access to parameter set was not possible. • Download application again (including module). • Send the device and a description of the fault to Lenze. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 73
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information Cause Remedy Station name is not DNS-conform. Use a DNS-compliant station name. Setting the station name ( 27) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 74
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information Cause Remedy Device is defective. Send the device and a description of the fault to Lenze. Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
(min. value | unit | max. value) 4294967295 0 Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 77
Active IP address.4 Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 78
Info C13850/1 C13850/8 Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 79
Reserved C13860/4 Reserved Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 80
Write cycles per second Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 81
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Bytes Information Slot Subslot Error code Slot Subslot Error code Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 82
Bit 15 Stack CPU boot error Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 83
1 PDOs are set to the value'0' Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 84
The code contains a string with a length of 8 characters. The identification code "E84DGFCR" is output. Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 85
I&M3 additional information Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 86
I&M4 signature code 0000000000000000000000000 Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Causes and remedies C13901 | Firmware compilation date Error messages (short overview) C13902 | Firmware version Error number C13910 | I&M1 system designation 0x01bc3100 Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 90
Internal switch latency Invalid write (error message) Interruption of internal communication Restart by watchdog reset (error message) Interruption of PROFINET communication Stack init error (error message) Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Page 91
Technical data Terminology used Terms Type of node Use of repeaters User data assignment User data length Validity of the documentation Versions Voltage supply Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23...
Perhaps we have not succeeded in achieving this objective in every respect. If you have suggestions for improvement, please e-mail us feedback-docu@lenze.com Thank you very much for your support. Your Lenze documentation team...