Honeywell MB-Secure 1000 Installation Instructions Manual page 14

Table of Contents

Advertisement

14
2.6.1.1 Programming jumpers/Monitoring resistors
Signalling devices 160455.10/160456.10 must not be used in systems according to VdS.
Installation Instructions MB-Secure 1000/2000/3000/4000/5000/6000
Programming jumpers P2/P3 terminating resistors RS-485
P2/P3 connected: Terminating resistors active
P2/P3 not connected: Terminating resistors inactive
Programming connection P4 signalling device type
Position A:
Signalling device 160455.10/160456.10*
Position B:
Signalling device 048700/048720
Monitoring resistors
If signaling device 160455.10/160456.10* is
connected, the following monitoring resistors in the
signaling device must be changed
R1
10k
R2
4k7
R3
0R
The corresponding resistors can be found in the
accessories pouch for the MB-Secure Siren module.
Programming connection P7 interface-operating mode
Position A:
Interface-operating mode BUS-2
Position B:
Interface-operating mode RS-485
(in preparation)
->
4k7
->
12k1
->
12k1