26
Connection BUS-2 User
Connection BUS-2 User with alternate U_ext-feed
Special information regarding IB2 topology
-
Utilization of cables J-Y(ST)Y, J-H(ST)H, J-2Y(ST)Y.
-
Cable diameter 0.6 mm and 0.8 mm.
-
Different cables should not be used together.
-
Star quad can be used (J-2Y(ST)Y).
-
Maximum line length 2000 m in total
-
The control panel can occupy any position on the BUS.
-
Terminating resistors (120 Ohm) have always to be placed at the end of the lines.
-
1 intermediate branch is permitted; it must not exceed 40 m in length.
-
Supply lines to the participants must not exceed 5 m.