Display Panel Not Responding

ISSUE
The heat pump's display panel will not respond to user input.
RESOLUTION
1. If heat pump display shows "
pump.
2. If needed, check with external controller manufacturer for further assistance using that device.
Displays Defrosting

Displays "DEFROSTING"

ISSUE
The heat pump has sensed the coil is icing up. See "Ice Forming on the Heat Pump" on page 41.
No action is required.
RESOLUTION
Heat and Cool Units - Active Defrost
Hot refrigerant gas will be sent through the coil to rapidly remove ice or frost.
During this process, the melting of the ice may appear as steam coming off the
heat pump. This is normal.
"NO SYSTEM
Displays
ISSUE
The heat pump has encountered a software error.
RESOLUTION
Call for service.
"NO POOL/SPA WATER
Displays
ISSUE
Low or no water detected. This is normal when circulation pump is deactivated.
RESOLUTION
1. Confirm the filter pump is on.
2. If a multiple-speed filter pump is being used, run at a higher speed to determine if the error persists. Do not
exceed maximum flow rate for your model.
3. Confirm water is not being diverted away from the heat pump.
See "Water Flow Rates" on page 28.
l
See "Adjusting Water Flow Using ΔT (Delta-T)" on page 29.
l
Page - 37