4. GENERATOR CONNECTION AND GROUNDING

WARNING
• Do not operate in standing water
• This generator is fitted with an neutral-earth connection at the alternator. Removal of this connection will
result in non-operable RCD's and risk of electrocution.
• All electrical work must be carried out by a qualified electrician.
The end user, equipment owner or operator must contact a licensed electrician to determine the approved
generator grounding and connection method to be used in their application or location.
The generator has been designed and manufactured in accordance with AS/NZS3000 and its reference
standards as relevant. Testing has been conducted in accordance with AS/NZS3017.
A neutral-earth connection has been installed at the alternator, and RCD's are fitted for each receptacle (socket
outlet). In accordance with AS/NZS3012, for generators supplying power through RCD protected receptacles it is not
required, nor recommended, to fit an earth stake to the generator. Please consult a licensed electrician for advice on
earthing requirements for other applications and installations.
2-M6
GENERATOR
9Y1211607GRM0007US0
KiSC issued 06, 2016 A