Troubleshooting

1.12 Field Setting Error

Remote Controller
Error Code
LCD Display
LED Indication
Remote Controller
Error Detection
Method
Error Generating
Conditions
I Faulty combination of remote controller
Possible Causes
I More than 16 units connected to remote controller cable.
I Faulty remote controller
Troubleshooting
<Combination-Right or Wrong>
Main body
Heat reclaim ventilation unit only
Heat reclaim ventilation unit only
Heat reclaim ventilation unit only
Heat reclaim ventilation unit + air-conditioner
Heat reclaim ventilation unit + air-conditioner
Heat reclaim ventilation unit + air-conditioner
42
U U U U A A A A
5
Inspection
Unit No.
1
5
Main Unit
Is
combination
of remote
NO
controller and heat
reclaim ventilation
unit (air
conditioner)
correct?
Refer "Combination-Right or Wrong"
YES
Are
17 or more
NO
units connected
to remote
controller
cable?
YES
1
Remote controller
Heat reclaim ventilation unit
Heat reclaim ventilation unit + air-conditioner
Air conditioner
Heat reclaim ventilation unit
Heat reclaim ventilation unit + air-conditioner
Air-conditioner
Check the system, and correct
connections.
Change connections so that 16
or fewer units are connected to
remote controller cable.
Replace remote controller.
(HF011)
Right/Wrong
Right
Wrong
Right
Wrong
Right
Right
Troubleshooting
Si-93